INFLUX MEASUREMENTS SprinklerSense FTI Скачать руководство пользователя страница 3

IOM FTI Iss.1 

October 2018 

Page 3 of 8 

Flow Switch Check 

While the green LED is flashing, turning the key to TEST will start a flow switch check. This should only be 
carried out by or with the permission of Fire Safety personnel, after the main panel has been set ready for the 
test. Failure to carry out this procedure in the correct order could result in a false alarm condition. If the key is 
left in this position, the unit will timeout back to its normal ON mode. To start a test if the key has been left in 
the TEST position and timed out, the key must be returned to ON position and then re-set to TEST. 

Flow Switch Test Procedure: 

 

 

 

Authorise 

•Gain permission from Fire Safety personnel 
•Set main panel ready for test, to avoid alarm sounding 

Test 

•Turn key to 'TEST' position 
•Wait for flowswitch set delay period 

CHECK

•Ensure that red LED starts to flash 
•Check that a flow alarm signal is indicated by main panel 

Reset 

•Return key to 'ON' position 
•Wait a few seconds for the Green light to flash 
•Return the main panel to normal condition 

Содержание SprinklerSense FTI

Страница 1: ...O THE INSTALLATION OPERATION MAINTENANCE OF SprinklerSense Fixed Test Interface Unit FTI FOR USE WITH SPDB30 SPDB90 TYPE FLOW SWITCHES Contents Page 1 Specification Operation 2 1 1 Introduction 2 1 2...

Страница 2: ...mA 1 3 Operation The FTI is connected to the SprinklerSense flow switch via a serial communications link wired It continuously requests status information from the sensor and reacts accordingly In nor...

Страница 3: ...the unit will timeout back to its normal ON mode To start a test if the key has been left in the TEST position and timed out the key must be returned to ON position and then re set to TEST Flow Switch...

Страница 4: ...tallation refer to the software installation guide If the software is installed but USB OK is not displayed when expected it is likely that the PC has not yet recognised that the device is connected T...

Страница 5: ...ed with a minimum depth of 35mm The box should be mounted in an easily accessible position where it is not likely to become wet in normal use Cable entries should be made available for cables 1 from t...

Страница 6: ...itch unit using J1 terminals 4 to 7 in the FTI to terminals 1 to 4 in the flow switch Connect V to V V to V COMS to COMS and COMS to COMS Shown in wiring diagram below Relay Outputs Connect the SPDB30...

Страница 7: ...on a separate block J5 for remote key switch actuation These terminals must only be connected to volt free contacts such as a mechanical switch or relay contacts Connection to other types of circuit...

Страница 8: ...that the power supply is correct and turned on If the Remote Key Switch input is connected disconnect and try unit again If the unit still does not function it should be replaced by a new unit FTI uni...

Отзывы: