Figure 1 - Mechanical outline drawing (inches)

RJ-45 Pin

Function

1

TX+

2

TX-

3

RX+

6

RX-

4, 7

+55V

5, 8

-55V (RETURN)

Shield

DRAIN

Table I    

                                

1. 

This product is intended for use only on data and DC power 

circuits with operating voltages not to exceed 55VDC and operating 

currents not to exceed 1A. The Product is UL 497 Listed. And is 

appropriate for use as either a primary or  secondary protector.

2.

 Mounting the ALPU-ALVR (See Diagram):  Mount the device as 

close to the equipment to be protected as possible using the 

provided hardware and the      concealed mounting holes.  Mount the 

unit in the orientation shown, with the marking “UP” facing upward 

and the strain reliefs facing the ground.

3. 

Wiring the ALPU-ALVR

     3.1 Removing the Cover: 

Loosen the 4 captive cover screws us  

       

       

     ing a Phillips screwdriver and lift off the cover.

     3.2 Wiring the Suppressor: 

Thread a multiconductor cable from  

                 

     the data source through the strain relief adjacent to the marking      

     on the PCB labeled Input. Strip back the cable jacket as needed,

     then install the conductors into the IDC connectors labeled Input 

     using the following technique: Lay the wires into the grooves in 

     the connector, leaving approximately 1/8” of wire overhanging, 

     and press down firmly with the punch-down tool provided in the 

     packaging supplies until the wires firmly engage into the fork 

     terminals.  Use the wiring tables in this document as well as the  

 

      

     callouts on the PCB as a guide. Repeat this procedure for the 

     outgoing multiconductor cable, using the connectors labeled Out 

        

      

     put. Tighten the strain reliefs to secure the cables (DO NOT OVER    

       

     TORQUE!!). Reinstall the cover.

     The ALPU-ALVR is intended to be used with the following Alvarion         

      

     Product Families:  BreezeMAX; BreezeACCESS VL; Breeze

     ACCESS 4900; BreezeNET B Series and DS.11 Version 

    

     3.3 Grounding: 

Connect the external ground lug on the enclosure 

     to a solid Earth ground. The unit must be grounded for the 

     suppressor to operate properly!

4.  

Use the pinout configuration in Table 1.

ALPU-ALVR  1101-640

1200-148 REV G