Figure 1 - Mechanical outline drawing (inches)

ALPU-POE-INJ

INSTALLATION NOTES

1. The ALPU-PoE-INJ is intended to be installedindoors or outdoors, on wall 

or pole mount applications. The unit features mounting feet on the sides that 

mount on 4” center-to-center holes with #10 sized hardware. The mount foot 

also adapts to 4” diameter pole mounting kits with a 4.5” center-to-center 

holes and larger hardware. Refer to figure 1 for mechanical requirements 

and connector locations. The optimum ground connection on the metal 

enclosure unit at the mounting flangeon either side is shown in Figure 1. 

Use minimum 8awg wire for a ground reference attachment. Communication 

cables with the RJ45 connectors already installed can feed directly into the 

enclosure. Be sure to install the cables with the unprotected cable installed 

into the left “in” jack and the protected equipment cable in the left “out” jack. 

The enclosure features a built in cable retention that grips the cable with a 

screw down bracket. Apole mount adapter kit (pn 1000-1164) is available 

to meet installations on a wide range of pole diameters from 2” metal fence 

poles to 10” diameter utility poles.

2. Mount the device as close to the equipment to be protected as possible 

using the provided hardware. Mount the unit in the orientation shown, with 

the strain reliefs facing the ground.

INSTALLATION INSTRUCTIONS

1.Remove the cover by removing the screw on the front of the unit.

2. Mount the unit to an outside surface using the two mounting holes shown 

in figure 1.

Note: if desired, remove knockouts for conduit

3. Connect the Ethernet cable between the indoor unit and the suppressor 

using the RJ45 jack.

4. Connect one Ethernet cable between the outdoor unit and the suppressor 

using an RJ45 jack.

Note- the suppressor is bi-directional and protects equally in both directions.

5. The ALPU incorporates a 1/4-20 ground stud. Attach appropriate wire 

guage and type as short as possible (less than 3 feet) between this stud and 

the site grounding point. Refer to local codes and equipment manufactures 

standards before installation

6. Replace cover 

1200-410 Rev E