Infiltrator AQUAworx IPC Panel Скачать руководство пользователя страница 19

Contact Infiltrator Water Technologies 1-800-221-4436 for additional technical and product information.

19

primary load draw is the pump and the most likely component to 

trip the supply circuit breaker. With two circuits, if the pump circuit 

tripped, power would be available to the controls and will notify the 

homeowner of the problem.

Why does my control panel read the EVENTs once a minute?

If the Log Status in the panel is set to Y (yes), then it will record 

every event once per minute.  This will cause the 4000 event to  

fill-up quickly in the panel.  The Log Status may be set to N (no).  

To change this using the MARC, go to Mode settings and press 

enter.  In the first screen named Log Status, if you press enter the 

Log Status can be changed to N (no). 

Why does my Transducer always read a 00.0” level?

In some cases the Transducer or circuit board may need to be 

replaced. Check all connections. Test any component before  

installing it. Checking a transducer with a bucket of water is an 

easy way to see if the new transducer solved the problem.

Why does the Transducer read a constant level, (ex: 1.5- 6.5”) 

even though the pump is running?  

The Transducer wiring to the circuit board is not in the proper  

sequence.  Make sure the input wires are RED (RD), BLUE (BL), 

and BLACK (BK) from left to right on the wire terminal strip  

attached to the circuit board.

How do you setup for a Redundant off Float? 

The best way to use a redundant off is to wire a load rated float 

switch in line with the power in the pump vault. Secondly, many 

pump companies supply a “piggy back float” option.

How do I wire a panel for 230/240 Volt installations?

The control side of the panel must only be wired for 120 volt  

installation. For the pump(s) power supply (Line side),  

using 3-wire, connect the Red wire to the Neutral or Pump L1  

terminal block and the Black wire to the Pump L2 terminal block.  

The White neutral wire can be cut back. 

What should I use to plug the conduit to prevent sewer gases 

from entering the enclosure?

There is a variety of conduit sealing compounds available, but we 

recommend, Chico SpeedSeal Compound, as it will quickly harden 

to a dense, strong mass and is UL Listed and cUL Listed.  

Can you run the same Transducer wire in the conduit for the 

pump supply?

The Transducer wire can be run thru the same conduit as the 

pump power supply without interference.  However, the  

Transducer is a low voltage wire and in some jurisdictions it is 

not allowed to run both High/Low voltages in the same conduit.  

Check with both regional and State Regulations first.

Can I setup the IPC panel with a Remote Alarm?

Yes, a remote alarm can be purchased as an option with all  

Aquaworx IPC panels. The remote alarm will provide the same 

alarm sequence as the alarms on the main enclosure.  The remote 

alarm can be located up to 2000’ away from the main control box.  

Contact customer service to purchase.

What is the difference between DOSE, ADOSE & BDOSE in the 

Event log?

Dose = A recorded standard Dose from pump A. 

ADose = A recorded Autoclear Dose.

BDose = A recorded Dose from pump B.

Can the panel be setup using two transducers?

Yes, using a IPC Sand filter panel specifically for installations that 

require two separate pump systems each needing a separate 

transducer for each pump.  (Product ID number: IPC-DSF)

When I set the panel up to run both pumps what will happen?

This setting is designed to run both pump A and pump B during a 

Veto level. This setting is used in conjunction with a Duplex panel 

to pump the tank down faster. This should only be used if the 

pumps are small and both pumps can run on one circuit or if it is a 

specialty panel setup for individual circuits for each pump.

Can I put a heater unit inside the control panel?

Yes, Aquaworx offers a heater unit that can be easily setup in an 

existing or new IPC panel.  Contact customer service for more        

information.

What is the battery on the circuit board, and/or will I lose my 

events if the power goes out?

Its purpose is to keep the clock running, which will allow the data 

logging to record when the power goes out and for how long the 

power was off.  The battery can last up to five years without a  

replacement but, it is recommend that it be change every year.  

If the battery is lost and the power goes out all data and all  

settings are retained and will function once power is restored,  

however, the date and time will re-set to 00.

What is a Varistor? 

A varistor is a variable resistor used to protect excessive current in 

a circuit. Our varistor is connected between the incoming line and 

neutral. This 130V varistor serves as over voltage/surge protection 

for the controller. 

How do I setup the panel to handle a Sand filter application?

Using the MARC controller, under the Mode settings, the Run Both 

/ SFI (Sand Filter Interface) menu will need to be set to Y (yes). This 

will not allow Pump A to initiate if pump B has a high level alarm.

The MARC unit is not recording events from my SD card?

If the MARC screen is going blank during the download, then it is 

probably receiving too much current from the SD card.  This may 

be caused by too much data on the card, or too much memory 

on the card.  We recommend a 1 Gigabit maximum SD card with 

dedicated use for the MARC.

How do I wire a Transducer to the panel for a Sand filter  

application?

Follow the instructions provided with the panel. If the  

instructions are lost we can email you, or download from our  

website, www.aquaworx.com

Содержание AQUAworx IPC Panel

Страница 1: ...RX MARC OPERATING INSTRUCTIONS GENERAL 6 MARC PLUG IN START UP 7 CONTROLLER PASSWORDS LOGIN SETUP 7 MENU OPTIONS MAPPING 8 CONTROLLER MENU OPTIONS 9 STATUS 10 EVENTS 10 MANUAL RUN 11 ACTIVATE SETTINGS 11 PUMP A SETTINGS 12 TIME SETTINGS 13 SD CARD OPERATIONS 13 USING THE SD CARD SETTINGS 14 SAND FILTER PANEL SETUP 15 TIMED DOSING SETUP FORMULATION 16 FREQUENTLY ASKED QUESTIONS 18 www infiltratorwa...

Страница 2: ...tem design requirements The Simplex Panel has the ability to time control a single pump while the Duplex Panel can control two pumps in an alternating design with independent timing The Sand Filter Panel has the ability to time control two individual pumps having independent level sensors allowing for a design which can time dose a treatment system and drainfield I General Unpack the Aquaworx IPC ...

Страница 3: ...supply enters the IPC Panel through the bottom approximately 1 to the right of the audible alarm unit 2 On Simplex Panels drill two holes 3 holes for duplex in the bottom of the enclosure spaced approximately 2 apart and in line with the audible alarm unit When facing the panel the order of conduit connections from left to right is shown below as well as illustrated in Figure 2 Power in 2 dedicate...

Страница 4: ...2 Feed the transducer signal wire and snorkel tube through the 1 PVC stand pipe and glue to the pressure transducer bell using a 1 tee The length of the stand pipe when secured should position the bottom of the pressure transducer bell above the top of the pump 3 Cut off the snorkel tube approximately 9 lower than the top of the stand pipe and secure it to the transducer signal wire The snorkel tu...

Страница 5: ...Panel The following Morse Code characters communicate specific system conditions Morse Code P _ _ Controller was just powered up On Continuous The water level is above the high level set point Morse Code S The level sensor is not communicating with the controller FIGURE 4 IPC PANEL WITH VISUAL ALARM NOTE SCB02 Panel uses a toggle switch on the side for the same function C Manual Pump HOA Feature P...

Страница 6: ...he panel using a standard RJ45 cable included The MARC includes a SD memory card slot allowing the user to capture and download system events and settings onto a removable card This provides the operator with a history of system function which is critical to troubleshooting and maintaining a pump driven system FIGURE 5 THE MARC Tracking SD card slot for event download LCD text display 2 line 20 ch...

Страница 7: ...e Figure 7 for complete MARC menu mapping SIMPLEX The SIMPLEX panel user may access the above menus in addition to the following menus A VIEW STATUS A B VIEW EVENTS C MANUAL RUN A OR B D ACTIVATE SETTINGS E PUMP A SETTINGS F TIME SETTINGS G SD CARD SETTINGS H LOGIN RJ45 Cable Connection to MARC DUPLEX The DUPLEX panel user may access the above menus in addition to the following menus STATUS B MANU...

Страница 8: ...on of events depending on the amount stored Manual Run Pump A or B Time State Level 000 00 MRun 00 00 Time State Level 000 00 MStop 00 00 Activate Settings Waiting Pumping Idle 001 30 Level 03 6 Pump A Settings Pump On Time 01 00 Veto On Time 01 00 Pump Off Time 060 00 Veto Off Time 030 00 High Level 20 0 Start Level 1 0 Veto Level 19 0 Zero Bias 07 08 09 Auto Clear Set Time Date 12 04 51 06 14 13...

Страница 9: ...Hands Off Auto switch See Section C Sets IPC Panel into auto mode after settings have been modified See Section D Setup functions for Pump A See Section E IPC Panel setup for establishing local time and date See Section F Set of sub menus designed to perform events and settings retrieval and to clear events when desired See Section G Allows user to access administrative settings to update advanced...

Страница 10: ...ound in this menu NOTE Status B is an available menu option on Duplex panels 300 AQUAWORX HUI R1 3 2 C c 2012 LIPS Time min sec State Pumping Waiting Idle Level Inches above bottom of bell Run Time hr min sec Doses Cycle counter normal dose V Cycle counter veto dose Date and time Number of events Software identification version and revision IPC Panel identification number Section B EVENTS A read o...

Страница 11: ...on will alternate between Pump A and Pump B with each cycle of the Enter button The screen display for Manual A and Manual B are similar as follows Time State Level 000 12 MRun 00 0 Manual Run Pump A or B Time Counter in that event state State MRun or MStop Section D ACTIVATE SETTINGS Allows the user to actuate or upload the controller settings to the IPC Panel Waiting Pumping Idle 001 30 Level 03...

Страница 12: ...id level is below the start level Pump On Time 001 00 Pump A Settings All values shown are the factory setting Pump Off Time 060 00 Veto On Time 002 30 Veto Off Time 030 00 High Level 20 0 Veto Level 19 0 Start Level 001 0 Zero Bias 07 Auto Clear 02 Doses Veto Dose The Veto function is simply a separate level that instructs the pump to run a different timing sequence and is intended to prevent pum...

Страница 13: ...RATIONS A set of sub menus designed to perform events and settings retrieval and to clear events when desired Save Events Y N SD Card Operations Clear Events Y N Save Settings Y N Saves events to SD card write events Y don t write events N Clears currents events from control board clear events Y don t clear events N Saves settings to SD card write settings Y don t write settings No Save all 4000 p...

Страница 14: ... and placed in a card reader connected to a PC 5 On the user s PC locate the designated drive for the card reader 6 Click on the file to identify the SD card events file evt and settings file set 7 The file can be opened using a spreadsheet or text editing program NOTE Each event and settings file is saved by IPC Panel serial number allowing the user to save the data from multiple IPC Panels on a ...

Страница 15: ...ne both Sensor A B Black wires with a wire nut and run a single wire to terminal 3 4 Connect the Blue wire from Sensor B to terminal 4 Terminals 5 6 remain open The Sand Filter features may be accessed and set up using the MARC interface and by using the following steps Figure 8 Sand Filter Panel Terminal 1 2 3 4 5 6 Figure 5 Terminal Strip 1 Plug in the MARC using the RJ45 Cat5e cord Screen shoul...

Страница 16: ...u ft 12 gal in Example 1 Assuming the tank is 96 long x 48 wide x 1000 gals 96 x 48 x 7 48 12 4608 144 x 7 48 12 32 x 7 48 12 239 36 12 19 9 gal in rounded up to 20 gal in W L R Table 1 Rectangular Square Tanks Width Feet inches Length Feet inches Gallons of liquid per inch 3 4 40 in 6 8 80 in 13 9 4 48 in 4 48 in 10 0 4 48 in 8 96 in 19 9 4 5 53 in 8 6 102 in 23 4 4 10 58 in 8 6 102 in 25 6 5 2 6...

Страница 17: ... when no water is being discharge to the system B The time from when the first squirt shows the first orifice until the laterals are equally pressurized By multiplying by 3 we are ensuring that 67 of the water is being equally distributed Example Pump is turned on and the first squirt shows in 5 seconds A 5 seconds The time from the first squirt until the system is pressurized is 10 seconds B 10 s...

Страница 18: ... the start level pump down to the bottom of the bell then wait through the OFF time then run the ad ditional time to clear the bell Can I cut or splice the transducer signal wire It is OK to cut the transducer wire to length from the tank to the panel However the cable should NOT be spliced The high potential of corrosion when splicing the signal wire will affect the signal and could reduce the ac...

Страница 19: ...m can be purchased as an option with all Aquaworx IPC panels The remote alarm will provide the same alarm sequence as the alarms on the main enclosure The remote alarm can be located up to 2000 away from the main control box Contact customer service to purchase What is the difference between DOSE ADOSE BDOSE in the Event log Dose A recorded standard Dose from pump A ADose A recorded Autoclear Dose...

Страница 20: ... Infiltrator Equalizer Quick4 and SideWinder are registered trademarks of Infiltrator Water Technologies Infiltrator is a registered trademark in France Infiltrator Water Technologies is a registered trademark in Mexico Contour MicroLeaching PolyTuff ChamberSpacer MultiPort PosiLock QuickCut QuickPlay SnapLock and StraightLock are trademarks of Infiltrator Water Technologies PolyLok is a trademark...

Отзывы: