13.
Fault Function
If there is a voltage drop (GV-value below 0,1V) from the sensor there is a fault situation. During the
first four hours the green LED will be deactivated,
and the other LED’s will flash. Alarm relay C will
change state. After four hours the LED “Alarm B” will light (other LED’s will
be deactivated) and relay
“Alarm B” will also change state.
14.
Fail Safe
Relays are in normal mode energized and will change state if power failure or if a fault situation
occurs.
15.
Technical Data
Housing HFC & NH3:
Polycarbonate, (PC) IP54
Power consumption:
Max 2W
Housing CO2:
Polycarbonate, (PC) IP67
Power consumption:
Max 3W
Power supply:
LDM150: 12-24V AC/DC
LDM150,HFC/NH3, High Voltage: 230V AC, 50/60 Hz
LDM150, CO2, High Voltage: 85-230V AC, 50/60 Hz
Indications:
Power/Active and alarm indication on three levels.
Outputs relay:
Potential free contacts (230V, max 5A) .
Ambient temp:
-
40 °C
- + 50 C (Automatic temperature compensation)
Humidity:
0-95% RH (non-condensing)
Glands:
4 of M16 membrane glands
Screw terminals:
< 1,5 mm2, fuse < 10A
Please Note!
The semi conductive sensors used in the LDM150 range of products are not gas
specific. Care should be taken when installing the equipment to minimize any cross
contamination from other gases or vapors.
For further guidance on specific applications contact us.
This product is intended for use in the industrial area.
Specifications subject to change.