9163
PROP_BAND_REG_HEAT
o
Heating proportional band
ǻ&>ǻ)@
(Note1)
114
20 [36]
10 [18]
200 [360]
R/W
9164
INTEGRAL_TIME_REG_HEAT
o
Heating integral time (s)
115
0
0
999
R/W
9165
PROP_BAND_REG_COOL
o
Cooling proportional band
ǻ&>ǻ)@
(Note1)
116
20 [36]
10 [18]
200 [360]
R/W
9166
INTEGRAL_TIME_REG_COOL
o
Cooling integral time (s)
117
0
0
999
R/W
9167
PROP_BAND_SUPPLY
o
3URSRUWLRQDOEDQGIRUWKHFDOFXODWLRQRIWKH
supply setpoint in cascade control
ǻ&>ǻ)@
(Note1)
118
200 [360]
10 [18]
500 [900]
R/W
9168
INTEGRAL_TIME_SUPPLY
o
Integral time for calculation of supply
setpoint in cascade control (s)
119
0
0
999
R/W
9169
ECO_SET_ADJUST
o
Economy or boost offset
ǻ&>ǻ)@
(Note1)
120
30 [5]
-120 [-22]
120 [22]
R/W
9170
HOL_SET_ADJUST
o
2IIVHWPRGHIRU³QRQRFFXSLHGKROLGD\´RSHUDWLRQ
ǻ&>ǻ)@
(Note1)
121
50 [9]
10 [2]
140 [25]
R/W
9171
DO_HYST
o
Hysteresis for on/off output
ǻ&>ǻ)@
(Note1)
122
10 [18]
5 [10]
20 [36]
R/W
9172
DEAD_ZONE
o
Neutral zone for 4-pipe systems
ǻ&>ǻ)@
(Note1)
123
10 [18]
5 [10]
50 [90]
R/W
9173
DIFF_INSERT_HEATING
o
'LIIHUHQWLDODGGLWLRQRIKHDWLQJLQVXPPHU
season (mid-season)
ǻ&>ǻ)@
(Note1)
124
30 [54]
5 [10]
100 [180]
R/W
9174
AUTHORIZE_LIM_SUPPLY_LOW
o
Activation of minimum supply limit for
¿[HGSRLQWFRQWURO
0=not enabled
1=enabled in cooling mode
HQDEOHGLQKHDWLQJPRGH
HQDEOHGLQKHDWLQJDQGFRROLQJPRGHV
125
0
0
3
R/W
9175
SET_LIM_LOW
o
Minimum low supply limit setpoint (°C [°F])
(Note1)
126
100 [50]
60 [43]
128
R/W
9176
AUTHORIZE_LIM_SUPPLY_HIGH
o
Activation of maximum supply limit for
¿[HGSRLQWFRQWURO
0=not enabled
1=enabled in cooling mode
HQDEOHGLQKHDWLQJPRGH
HQDEOHGLQKHDWLQJDQGFRROLQJPRGHV
127
0
0
3
R/W
9177
SET_LIM_HIGH
o
+LJKVXSSO\OLPLWVHWSRLQW
(°C [°F])
(Note1)
128
400 [86]
126
500 [122]
R/W
9178
3523B%$1'B/,0
o
3URSRUWLRQDOEDQGIRUWKHOLPLWǻ&>ǻ)@
(Note1)
129
20 [36]
10 [18]
200 [360]
R/W
9179
AUTHORIZE_SETPOINT_COMPENSATION
o
Activation of compensation
IRURSHUDWLRQVZLWK
014
=1 or 4
0=not enabled
1=enabled in cooling mode
HQDEOHGLQKHDWLQJPRGH
HQDEOHGLQKHDWLQJDQGFRROLQJPRGHV
130
0
0
3
R/W
9180
TEMP_EXT_MIN_COMP_HEATING
o
Minimum external temperature for
winter compensation (°C [°F])
(Note1)
131
-100 [14]
-100 [14]
I32
R/W
9181
TEMP_EXT_MAX_COMP_HEATING
o
Maximum external temperature for
winter compensation (°C [°F])
(Note1)
132
200 [68]
I31
50.0 [122]
R/W
9182
SET_TEXT_MIN_COMP_HEATING
o
Compensation setpoint
FRUUHVSRQGLQJWRWKHPLQLPXPH[WHUQDOWHPSHUDWXUHIRUZLQWHU
compensation (°C [°F])
(Note1)
133
600 [140]
50 [41]
800 [176]
R/W
9183
SET_TEXT_MAX_COMP_HEATING
o
Compensation setpoint
FRUUHVSRQGLQJWRWKHPD[LPXPH[WHUQDOWHPSHUDWXUHIRUZLQWHU
compensation
(°C [°F])
(Note1)
134
300 [86]
50 [41]
800 [176]
R/W
9184
TEMP_EXT_MIN_COMP_COOLING
o
Minimum external temperature for
summer compensation (°C [°F])
(Note1)
135
220 [72]
-100 [14]
I36
R/W
9185
TEMP_EXT_MAX_COMP_COOLING
o
Maximum external temperature for
summer compensation (°C [°F])
(Note1)
136
350 [95]
I35
500 [122]
R/W
9186
SET_TEXT_MIN_COMP_COOLING
o
Compensation setpoint
FRUUHVSRQGLQJWRWKHPLQLPXPH[WHUQDOWHPSHUDWXUHIRUVXPPHU
compensation (°C [°F])
(Note1)
137
190 [66]
50 [41]
800 [176]
R/W
9187
SET_TEXT_MAX_COMP_COOLING
o
Compensation setpoint
FRUUHVSRQGLQJWRWKHPD[LPXPH[WHUQDOWHPSHUDWXUHIRUVXPPHU
compensation
(°C [°F])
(Note1)
138
160 [61]
50 [41]
800 [176]
R/W
9188
AUTHORIZE_DEHUMIDIFICATION
o
$FWLYDWLRQRIGHKXPLGL¿FDWLRQ
0=not enabled
HQDEOHGZLWKEXLOWLQKXPLGLW\VHQVRU
HQDEOHGZLWKUHPRWHKXPLGLW\VHQVRU
HQDEOHGZLWKEXLOWLQKXPLGLW\VHQVRULQFRROLQJRQO\
HQDEOHGZLWKUHPRWHKXPLGLW\VHQVRULQFRROLQJRQO\
139
0
0
4
R/W
9189
AUTHORIZE_HUMIDIFICATION
o
$FWLYDWLRQRIKXPLGL¿FDWLRQ
0=not enabled
HQDEOHGZLWKEXLOWLQKXPLGLW\VHQVRU
HQDEOHGZLWKUHPRWHKXPLGLW\VHQVRU
140
0
0
2
R/W
9190
DEAD_ZONE_HUM
o
1HXWUDO]RQHKXPLGLW\
(Note2)
141
60
40
200
R/W