INSTRUCTION

i

Read this instruction before installation 

and wiring of the product

CTR-ADD

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken

1

CTR-ADD

Triac controller for proportional control 

of electric heating, add-on unit

CTR-ADD is a complete proportional controller for electric heating. 
It has automatic voltage adjustment. It has no sensor input but is 
intended to be controlled by another CTR unit.
CTR-ADD is only intended for electric heating control. The control 
principle makes it unsuitable for motor- or lighting control.
CTR-ADD cannot  control 3-phase loads.

Installation

Remove the front. The locking screw is behind the set-point knob. 

Mount CTR‑ADD vertically with the cooling flange at the top. Use 

screws with a maximum head diameter of 5.5mm.

 CTR-ADD emits approx. 20W of heat which must be dissi-

pated. Ambient temp.: 0 - 30°C, non-condensing.
Protection class: IP20.

Wiring

Supply voltage

Terminals 1 and 2. Not polarity sensitive.
Supply voltage: 200 - 415V AC, 50 - 60 Hz with automatic voltage 
adjustment. Maximum current 16A.

Control principle

CTR-ADD pulses the full load On - Off parallel to the master unit it is 
connected to.

CTR‑ADD has zero phase‑angle firing to eliminate RFI.

Start-up and fault finding

 Be careful when working in the CTR-ADD. All internal compo-

nents including the cooling flange are at line voltage potential. Never 

leave the unit under power without the front cover on.

1.  Check that all wiring is correct.
2.  Measure the resistance between terminals 3 - 4: At 230V: 

14.4

<R<230

.  At 400V:25

<R<400

.

3.  Connect supply voltage and twist the setpoint knob of the master 

unit between end stops. Check that the LED on the side of CTR-
ADD goes on and off at the same time as the LED of the master 

unit. Check with a clamp‑on ammeter that current is flowing to 

the heater.

Anything wrong?

1.  Disconnect supply power. Remove the control signal wiring from 

terminals I and I. Reconnect power. The LED should be continu-

ously off and no current should flow to the heater. Disconnect 

power and connect the terminals I and I to the terminals 1 and 2. 
Reconnect power. The LED should be continuously on and full 

current should flow to the heater.

2.  If everything is OK this far the CTR-ADD is OK and the fault 

must be found elsewhere.

 

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low Volt-
age Directive (LVD) standards EN 60669-1 and EN 60669-2-1.

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Direc-
tive 2004/108/EC through product standards EN 61000-6-1 and 
EN 61000-6-3.

RoHS

This product conforms to the Directive 2011/65/EU of the European 

Parliament and of the Council.

Contact

AB Industrietechnik Srl

Via Julius Durst, 70 - 39042 Bressanone (BZ) - Italy

Tel.  +39 0472/830626 ‑ Fax +39 0472/831840

www.industrietechnik.it - [email protected]

11876C

 

OCT

 15

EN

    

I I

1 2 U 3 4 U

Figure 1: Wiring of supply voltage and load

 The supply voltage to CTR-ADD should be wired via an all-pole 

switch with a minimum contact gap > 3mm. The cooling flange is live.

Load

Terminals 3 and 4.
Resistive single- or two-phase heater
Maximum load: 

3680W at 230V  (16A) 

 

 

6400W at 400V  (16A)

Minimum load: 

230W at 230V  (1A) 

 

 

400W at 400V  (1A)

Control signal

Terminals I and I. Not polarity sensitive.

Wire to terminals U and U in the main unit.

    

CTR...

CTR-ADD

1 2 U 3 4 U

I I

K 1 2 U 3 4 U K G G

Figure 2: Wiring of control signal

 CTR-ADD is galvanically separate from the main unit. They may 

therefore be supplied from different phases. The CTR-ADD control signal 
has high potential compared to neutral and earth (>200V). Thus, wiring of 
the control signal must comply with local codes for line voltage installa-
tions. The control signal must be wired so that the signal is cut when the 
supply voltage is cut.

Содержание CTR-ADD

Страница 1: ...with a clamp on ammeter that current is flowing to the heater Anything wrong 1 Disconnect supply power Remove the control signal wiring from terminals I and I Reconnect power The LED should be continu ously off and no current should flow to the heater Disconnect power and connect the terminals I and I to the terminals 1 and 2 Reconnect power The LED should be continuously on and full current shoul...

Страница 2: ...ro e alla terra 200V Pertanto il cablaggio del segnale di controllo deve essere eseguito in conformità ai regolamenti locali sulle installazioni con tensione di linea Il segnale di controllo deve essere cablato in modo da venire interrotto quando la tensione di alimentazione si disinserisce Principio di controllo Il CTR ADD attiva e disattiva il carico tramite impulsi parallelamente all unità prin...

Страница 3: ...it Der CTR ADD ist ein kompletter Regler für die Regelung von Elektro heizregistern mit automatischer Spannungsnachführung Er verfügt über keinen Fühlereingang ist aber zur Steuerung von einem anderen Regler geeignet Der CTR ADD ist nur zur Heizungsregelung geeignet Das Regelprinzip schließt eine Lichtsteuerung aus Nicht geeignet zur 3 Phasensteuerung Einbau Entfernen Sie die Front Die Fixirschrau...

Страница 4: ...reils quand l alimentation générale est coupée Princip de regulation Le CTR ADD module les temps de fonctionnement et les temps d arrêt en parallèle avec le CTR Maître Le CTR ADD commute la puissance au point zéro de l alternance afin d éviter les perturbations Mise en route et recherche de défaut de branchement Faire attention lorsqu il travaille avec le CTR ADD Tous les composants internes y com...

Отзывы: