CMF10
AB Industrietechnik Srl
Via Julius Durst, 70 - 39042 Bressanone (BZ) - Italy
Tel. +39 0472/830626 - Fax +39 0472/831840
E-mail: [email protected]
Homepage: www.industrietechnik.it
(mm)
122
120
64
Wiring
CMF10
Dimensions
Terminal Designation Operation
10
Common
11
NO
Change-over relay, 5A
12
NC
13
G
Reference for DO1 and DO2
14
DO1
Digital output
15
DO2
Digital output
20
AGND
Reference for AO1 and AO2
21
AO1
0...10 V DC output
22
AO2
0...10 V DC output
40
DI2
Digital input
41
DI+
Reference for DI1 and DI2
42
DI1
Digital input
43
UI+
Reference for UI1
44
UI1
Universal input PT1000 or Digital
50
AGND
Reference for AI1
51
AI1
PT1000 temperature sensor input
52
AGND
Reference for AI2 / SPI
53
AI2
PT1000 temperature sensor input
54
SPI
Input PT1000 setpoint device
Terminal Designation Operation
0
G
24 V AC
CMF10 only
1
G0
2
CMF10-230V
Terminal Designation Operation
0
L
230 V AC
CMF10-230
only
1
N
2
Product documentation
Document
Type
Manual
Manual CMF10
Instruction
Instruction CMF10