CMF10

CMF10 

Pre-programmed, configurable controller for 
simple applications

•  Language independent

•  Simple configuration via the backlit display

•  Input for an external setpoint device

The CMF10 range of controllers can be set to handle 

everything from temperature or humidity control to 

control of CO

2

 or pressure. They are intended for DIN-

rail mounting.

•  Pre-loaded with several application modes

•  24 V or 230 V AC supply voltage

•  Week-based clock / calendar function

CMF

CMF10 is a pre-programmed controller that can be used 
for control of temperature, CO

2

, pressure, and humidity 

in air handling and heating applications. It is a stand-alone 
controller for simpler applications. CMF is extremely easy 
to install, commission and control.
CMF uses a display with an encoder knob, making 
its built-in menu system very easy to use. Settings 
are entered by turning the encoder knob to a desired 
parameter/value. A value is then approved by pressing the 
knob.

Models

The CMF series comprises two different types, CMF5U 
and CMF10. 
CMF5U has 5 in-/outputs and CMF10 has 10 in-/outputs. 
CMF10 is available in two versions:

•   CMF10 with 24 V AC supply voltage 
•   CMF10-230 with 230 V AC supply voltage

CMF has been developed according to our Ready-Steady-

Go concept, which simplifies every step from installation to 

management.

Applications CMF10 and CMF10-230

CMF10 is pre-programmed with a choice of five different 
control modes:

1.  Supply air control
2.  Supply air control with outdoor compensation
3.   Cascaded room / extract air temperature control
4.   Radiator circuit control
5.  Domestic hot water control

Inputs and outputs

CMF10 has

•   2 analogue inputs, PT1000
•   1 SPI input for an external setpoint device
•   1 universal input, PT1000 or digital
•   2 digital inputs
•   3 digital outputs
•   2 analogue outputs, 0…10 V DC

Internal clock

CMF10 has a built-in week-based real-time clock with a 
number of different scheduler alternatives.

Easy to install

CMF is suitable for DIN-rail or cabinet mounting. Since 
the terminals are detachable all connections can be made 
before CMF is installed.

 revision

 

 

10 2015

Содержание CMF10

Страница 1: ...essing the knob Models The CMF series comprises two different types CMF5U and CMF10 CMF5U has 5 in outputs and CMF10 has 10 in outputs CMF10 is available in two versions CMF10 with 24 V AC supply voltage CMF10 230 with 230 V AC supply voltage CMF has been developed according to our Ready Steady Go concept which simplifies every step from installation to management Applications CMF10 and CMF10 230 ...

Страница 2: ...an symbol control modes 1 2 and 3 only is lit as long as the fan indication input is activated To see the values and status of all in and outputs simply turn the knob counter clockwise until the text I O is displayed and then press it To return to the Base display click on the knob and then turn it clockwise Display handling All setting and configuration is performed using the display and encoder ...

Страница 3: ...igital outputs Damper control with settable minimum supply air amount Control of frost protection or frost protection thermostat with manual reset High temperature limit switch Electric heater cool down function Digital scheduler Start stop of fan via built in relay for 230 V AC Digital input for extended running via timer Input for an external setpoint device Alarm management in the display as we...

Страница 4: ...ng 2 Cooling 3 Heating Cooling 4 Heating Heating 5 Cooling Cooling 6 Heating Dampers 7 Cooling Dampers 3 position control Instead of the analogue outputs CMF can be configured for 3 position control increase decrease Only the following output choices will then be available Heating Cooling DO1 is used for increase signal and DO2 for decrease This option cannot be combined with alarm output A single...

Страница 5: ...sensor can also be connected to UI1 permitting the room temperature offset to correct the supply temperature Wire UI1 as an analogue input 3 position control Instead of the analogue outputs CMF can be configured for 3 position control increase decrease DO1 will then be used for the increase signal and DO2 for the decrease signal This option cannot be combined with an alarm output Domestic hot wate...

Страница 6: ...oduct conforms to the requirements of the EMC Directive 2004 108 EC through standards EN 61000 6 1 and EN 61000 6 3 RoHS This product conforms to the Directive 2011 65 EU of the European Parliament and of the Council Inputs Analog inputs Three AI1 PT1000 sensor working range 0 84 C accuracy 0 5 C AI2 PT1000 sensor working range 30 54 C accuracy 0 5 C SPI PT1000 setpoint device working range 0 40 C...

Страница 7: ...O1 and AO2 21 AO1 0 10 V DC output 22 AO2 0 10 V DC output 40 DI2 Digital input 41 DI Reference for DI1 and DI2 42 DI1 Digital input 43 UI Reference for UI1 44 UI1 Universal input PT1000 or Digital 50 AGND Reference for AI1 51 AI1 PT1000 temperature sensor input 52 AGND Reference for AI2 SPI 53 AI2 PT1000 temperature sensor input 54 SPI Input PT1000 setpoint device Terminal Designation Operation 0...

Отзывы: