Ref. 004001001200   

 

 

 

 

 

     Rev.3: 17-01-2021       

 

39 

 

Provide adequate clearance for cooling and wiring ARDBOX & DALI 20 I/Os Analog HF PLUS. Is 
designed for natural convection cooling. For proper cooling, you must provide a clearance of at 
least 25 cm above and below the devices. Also, allow at least 25 cm of depth between the 
front of the modules and the inside of the enclosure. 

 

Notes for maintenance: 

 
A well-planned and executed maintenance program is essential to the satisfactory operation of 
solid-state electrical equipment. The kind and frequency of the maintenance operation will 
vary with the kind and complexity of the equipment as well as with the nature of the operating 
conditions. Maintenance recommendations of the manufacturer or appropriate product 
standards should be followed. 
 
The following factors should be considered when formulating a maintenance program:  
 

Maintenance must be performed by qualified personnel familiar with the construction, 
operation, and hazards involved with the control.  

 Maintenance should be performed with the control out of operation and 
disconnected from all sources of power.  

Care should be taken when servicing electrostatic sensitive components. The 
manufacturer's recommendations for these components should be followed.  

Ventilation passages should be kept open. If the equipment depends upon auxiliary 
cooling, e.g., air, water, or oil, periodic inspection (with filter replacement when 
necessary) should be made of these systems.  

The means employed for grounding or insulating the equipment from ground should 
be checked to assure its integrity. 

Accumulations of dust and dirt on all parts, including on semiconductor heat sinks, 
should be removed according to the manufacturer's instructions, if provided; 
otherwise, the manufacturer should be consulted. Care must be taken to avoid 
damaging any delicate components and to avoid displacing dust, dirt, or debris in a 
way that permits it to enter or settle into parts of the control equipment. 

Enclosures should be inspected for evidence of deterioration. Accumulated dust and 
dirt should be removed from the top of the enclosures before opening doors or 
removing covers.  

Certain hazardous materials removed as part of maintenance or repair procedure (e.g., 
polychlorinated biphenyls (PCBs) found in some liquidfilled capacitors) must be 
disposed of as described in Federal regulations. 

 

Safety rules for maintenance personnel 

 

Consider the following steps to follow. A false manoeuvre could be the cause of an 
accident or material damage. 
Do not disassemble or modify the modules. This could lead to breakdowns or 
malfunctions and could lead to injuries or fire. 

 

- All types of radio communication devices, including mobile phones and personal 
handy-phone systems (PHS), must be kept more than 

25cm

 away from the PLC in all 

directions. Failure to observe this precaution exposes malfunctions caused by excess of 
temperature. 

Содержание DALI 20

Страница 1: ...PLC ARDUINO ARDBOX DALI 20 I Os ANALOG HF PLUS MODBUS PLC ARDUINO ARDBOX DALI 20 I Os ANALOG HF PLUS...

Страница 2: ...Ref 004001001200 Rev 3 17 01 2021 1...

Страница 3: ...DALI 20 I Os Analog HF PLUS User Guide Revised January 2022 This user guide is for version PLC Arduino ARDBOX DALI 20 I Os Analog HF PLUS ABOX 103 001 8 with Reference name 004001001200 For older ver...

Страница 4: ...ms Persons who install or connect automation devices Persons who manage working automation installation Warnings Unused pins should not be connected Ignoring the directive may damage the controller Im...

Страница 5: ...au Guide de l utilisateur du contr leur pour les consid rations de c blage Avant d utiliser ce produit il incombe l utilisateur de lire le Guide de l utilisateur du produit et la documentation qui l...

Страница 6: ...LED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM Industrial Shields shall not be responsible for conformity with any codes regulations or standards that apply to the combination of prod...

Страница 7: ...ety instructions and warnings included in it Due to their training and experience qualified personnel are in a position to recognize risks resulting from the handling or manipulation of such products...

Страница 8: ...ive components of a PDS 1 Unintentional movements of driven machine components during commissioning operation maintenance and repairs caused by for example Hardware defects and or software errors in t...

Страница 9: ...ED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE INDUSTRIAL SHIELDS DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED Limitations of Liability INDUSTRIAL SHIELDS SHALL NO...

Страница 10: ...18 7 Ardbox Analog I O pinout 19 Zone Connections 19 8 Switch configuration 21 General Switches Configuration 21 RS 485 Switch configuration 23 RS 232 Switch configuration 23 I2C Switch configuration...

Страница 11: ...bit 0 10Vcc 0 to 10Vac Input Impedance 39K Separated PCB ground Rated Voltage 10Vac 5 to 24Vdc I min 2 to 12 mA Galvanic Isolation Rated Voltage 24 Vdc Interrupt isolated Input HS 24Vcc 5 to 24Vdc I m...

Страница 12: ...the AC terminals and the protective ground terminal Dielectric strength 2 300 VAC at 50 60 Hz for one minute with a leakage current of 10mA max Between all the external AC terminals and the protective...

Страница 13: ...dard No Standard Title Standard Reference No Symbol Title Symbol Meaning IEC 60417 Graphical symbols for use on equipment 5031 Direct Current Indicates that the equipment is suitable for direct curren...

Страница 14: ...anual is intended for technicians which must have knowledge on electrical systems General Precautions The user must operate Ardbox according to the performance specifications described in this manual...

Страница 15: ...Basically it is no needed to define the pins and if those pins are inputs or outputs Everything is set up automatically if using the boards In order to install Industrial Shields boards these are the...

Страница 16: ...Ref 004001001200 Rev 3 17 01 2021 15 5 Search for industrialshields 6 Click install selecting the latest version Following these steps you will be able to use now the Industrial Shields Boards...

Страница 17: ...Analog HF PLUS Board Ardbox Analog HF w HW RS 232 DALI or Ardbox Analog HF w HW RS 485 DALI depending on your jumpers switch configuration Also there are some examples of programming in File Examples...

Страница 18: ...v 3 17 01 2021 17 5 How to connect PLC Arduino to PC Connect USB port from PLC to PC NOTE Ardbox Family uses micro USB cable Open Arduino IDE interface Select Industrial Shields boards Ardbox Family S...

Страница 19: ...ies regardless of where use of the device is intended The equipment must be powered from an external power source in accordance with IEC 61010 1 whose output is MBTS and is limited in power according...

Страница 20: ...DCOM 24VCOM 3 5 6 9 10 11 13 1 0 7 3 5 6 9 10 11 13 Analog Out Analog Out Analog Out Analog Out Analog Out Analog Out Analog Out Digital Output Digital Output Digital Output PWM digital Output PWM dig...

Страница 21: ...3 26 24 29 2 RS485 A RS485 B RS485 Y RS485 Z SCL I2C SDA I2C Ground 5Vout DC RESET SPI Not Connected Not Connected Analog Digital Input Analog Digital Input Analog Digital Input Analog Digital Input A...

Страница 22: ...If this switch is ON the RS 485 RE is activated otherwise the I0 9 will be activated 3 RS 485 RE I0 9 If this switch is ON the I0 9 is activated otherwise the RS 485 RE will be activated Note To work...

Страница 23: ...switches number 1 and 3 at ON and number 4 and 2 at OFF RIGHT ZONE SWITCH RIGHT ZONE The right zone configures the outputs If the switch is set to ON the Q0 X will have the behaviour of a digital outp...

Страница 24: ...s of the top zone are configured as it is shown in the table RS 232 LEFT ZONE In order to enable the RS 232 communication protocol it is necessary that the switches of the left zone is configured as i...

Страница 25: ...th configuration switches I0 0 and Q0 6 will not be available In order to implement this communication a 4 7k pull up resistor IS ACI2C 4 7K is required TOP ZONE SWITCH MODE I0 2 RS RS I0 2 I0 3 RS RS...

Страница 26: ...ted to the D1 D0 This jumper zone makes the choosing between connecting the inputs Q0 9 Q0 8 to pins 4 and 8 of the Arduino Leonardo respectively or connect the RS 232 ports to activate the Software S...

Страница 27: ...RS 485 Switch configuration Jumper configuration o Available communication protocols Hardware Serial RS 485 I2C If I2C is active I0 0 Q0 6 are disabled TTL SoftwareSerial USB In order to enable the Ha...

Страница 28: ...ilable communication protocols Hardware Serial RS 232 I2C If I2C is active I0 0 Q0 6 are disabled TTL USB Jumper configuration ZONE 1 ZONE 2 Note The switches of the left zone of the RS 485 don t inte...

Страница 29: ...ot pull up so in order to work with the I2C an external pull up resistor is required If it is meant to work as a GPIO at 5V the switches must be set as I2C section 8 These pins are not stablished with...

Страница 30: ...ion Now they are part of DALI communication sending and receiving data with Manchester codification There is a connector with 2 DALI pins DA and DA This can be used with one of our DALI modules or an...

Страница 31: ...Ref 004001001200 Rev 3 17 01 2021 30 PWM Waveform Analog Out Turn on Analog Out Turn off...

Страница 32: ...Ref 004001001200 Rev 3 17 01 2021 31 Analog Digital Input Turn on Analog Digital Input Turn off...

Страница 33: ...Ref 004001001200 Rev 3 17 01 2021 32 13 Typical Connections...

Страница 34: ...Ref 004001001200 Rev 3 17 01 2021 33...

Страница 35: ...Ref 004001001200 Rev 3 17 01 2021 34...

Страница 36: ...Ref 004001001200 Rev 3 17 01 2021 35...

Страница 37: ...406 connector from Phoenix contact FK MC 0 5 10 ST 2 5 Connection details Article reference MC 0 5 10 G 2 5 THT Height 8 1mm Pitch 2 5mm Dimension 22 5mm Pin dimensions 0 8x0 8mm Pin spacing 2 50mm Ar...

Страница 38: ...Ref 004001001200 Rev 3 17 01 2021 37 15 ARDBOX Family Dimensions 45mm width DIN rail mounting...

Страница 39: ...dedicated electric cabinet and keep the cabinet ventilated If the location has high ambient temperature or heat generating equipment nearby install forced convection devices on top or sides of the ca...

Страница 40: ...g e g air water or oil periodic inspection with filter replacement when necessary should be made of these systems The means employed for grounding or insulating the equipment from ground should be che...

Страница 41: ...Insufficient tightening can lead to loose parts or wires and cause malfunctions Excessive tightening can damage the screws and or the module with the risk of falling short circuits and malfunctions Be...

Страница 42: ...Ref 004001001200 Rev 3 17 01 2021 41 17 Revision Table Revision Number Date Changes 1 30 08 2019 First implementation 2 03 07 2020 Second implementation 3 17 01 2022 Third implementation...

Страница 43: ...01 2021 42 About Industrial Shields Direction F brica del Pont 1 11 Zip Postal Code 08272 City Sant Fruit s de Bages Barcelona Country Spain Telephone 34 938 760 191 34 635 693 611 Mail industrialshie...

Отзывы: