CONNECTING POWER TO MOTOR
To connect motor for proper voltage and rotation, refer to the connection diagram on the
nameplate or inside the terminal/conduit box.
Motor
25 Feet
50 Feet
100 Feet
150 Feet
200 Feet
HP
115V
230V
115V
230V 115V 230V 115V
230V
115V
230V
1
10
14(16)*
6
12
4
10
2
8
1
6
1 1/2
8
14
6
12
3
8
1
6
1/0
6
2
8
14
4
10
2
8
1/0
6
2/0
4
3
6
12
3
8
1/0
6
2/0
4
4/0
3
5
-
10
-
6
-
4
-
2
-
1
7 1/2
-
8
-
6
-
3
-
1
-
1/0
10
-
8
-
4
-
2
-
1/0
-
2/0
Table B - Minimum Wire Sizes for Single Phase Motors
* Type S, SO, SJ, SJO, etc. Flexible cable wire sizes. See NEC Article 400 for ampacity.
NOTE:
NEC Article 310-5 --- Minimum conductor size for general wiring at 115-440VAC is
No. 14AWG.Above wire sizes based on approximate 5% voltage drop during starting; copper
conductors; and 75° C type THHW, THW, THWN, RH, RHW insulation, etc. For aluminum
wire, increase two wire size steps minimum. See NEC Article 310 for ampacities of aluminum
conductors.