Carrying out recordings
Intelligent current clamp meter ISMZ I – User Manual
13
6.1.2.1
Specifying the trigger thresholds manually
Select the LEVEL with the arrow buttons (6) and (10).
After pressing Enter (8)
on LEVEL, the current value can be set by
the arrow buttons (6), (7), (9) and (10) that should actuate the
trigger if exceeded. Confirm by pressing Enter (8).
Select the SLOPE with the arrow buttons (6) and (10).
After pressing Enter (8)
on SLOPE, the current change in A/ms
can be set by the arrow buttons (6), (7), (9) and (10) that should
actuate the trigger if exceeded. Confirm by pressing Enter (8).
The recording is started and stopped by REC (4).
6.1.2.2
Teaching of trigger thresholds
When trigger threshold are taught, the ISMZ I registers all current levels and current changes during the
process. Before the teaching process, specify by which amount the trigger thresholds should be higher
than the registered values (e.g. by 20 % higher). Furthermore you set a specific teaching time or start and
stop the teaching manually.
Switch into the LEARNING menu with the Mode button (2).
Select THRESHHOLD ADD with the arrow buttons (6) and (10).
Use the arrow buttons (7) and (9) to set by how much the
operationally prevailing current needs to be exceeded so that a
start trigger is actuated (e.g. 20 %). Values between 0 % and 95 %
are possible.
Select TIME with the arrow buttons (6) and (10).
Use the arrow buttons (7) and (9) to set how long the ISMZ I
"observes" the operational currents to generate a trigger threshold
from that.
(
Example:
Set the time in a production line so that ten complete
production cycles are recorded.) The following values are
possible:
5
minutes
10
minutes
15
minutes
20
minutes
25
minutes
30
minutes
As an alternative, the teaching time can be set to MANUAL. The
teaching mode runs until it is stopped manually.
Select START with the arrow buttons (6) and (10).
The maximum current value as well as the highest incline are
displayed in the display during the teaching.
After completing the teaching, the trigger thresholds are adopted
for the REC. CONFIG menu and the recording starts
automatically.
For a manual teaching time, the recording can be started and
stopped by REC (4).