Incon TS-STS Скачать руководство пользователя страница 7

Leak Testing /
Console Operation

 Continued...

ACK

SHIFT

SELECT SUMP REPORT

TEST

LEVEL

M1

LEFT

M2

RIGHT

M3

M4

J

W

REPORT

9

SELECT SUMP

SUMP 1

SUMP 2

SUMP 3

ALL

M1

LEFT

M2

RIGHT

M3

M4

SELECT ALARM TYPE

SYSTEM

SUMP

ALL

M1

LEFT

M2

RIGHT

M3

M4

SELECT (SYSTEM / SUMP) ALARM STATUS

ACTIVE

CLEARED

HISTORY

M1

LEFT

M2

RIGHT

M3

M4

6.)

To view an alarm/warning, 

press

 the 

M1 

or 

M2 

Key under the

word Alarm / Warning. While viewing the alarm, 

press

 the 

ACK

SHIFT 

key at the keypad to acknowledge. 

Cleared and

transient alarms should be acknowledged prior to starting
another test.

7.)

Press 

the 

Report 

key at the keypad to show various report

choices.

Reports

4

INCON

INTELLIGENT CONTROLS INC.

P.O. BOX 638

SACO ME 04072

1-800-984-6266

10/31/2001

12:15 PM

SUMP LEAK TEST REPORT

SUMP 2

TEST STARTED

12:00 PM

TEST STARTED

10/31/01

BEGIN LEVEL

7.0230 IN

END TIME

12:15 PM

END DATE

10/31/01

END LEVEL

7.0209 IN

LEAK THRESHOLD

0.002 IN

TEST RESULT:

FAILED

Reports can printout automatically or on
demand from the keypad. The
Sump Leak Test 

and Alarm

Reports print automatically.
The other reports, such as
the Sump Level Reports,
Alarm Reports, and Sump
Test Reports can be printed
on demand.

Press the menu select keys
and choose the type of report
that you wish to printout.
Alarm reports will print as
soon as an alarm is detected.
Leak test reports print
automatically after the leak test is finished. 

Note that

when a new leak test is complete the data will
overwrite a previous result.

Of the three reports shown here, one is a Level
Summary report and two are Sump Leak Test
Reports.

Up to 4 sumps can be leak-tested at the same
time.

REPORTS continued...

INCON

INTELLIGENT CONTROLS INC.

P.O. BOX 638

SACO ME 04072

1-800-984-6266

10/31/2001

12:15 PM

SUMP LEAK TEST REPORT

SUMP 1

TEST STARTED

12:00 PM

TEST STARTED

10/31/01

BEGIN LEVEL

2.0120 IN

END TIME

12:15 PM

END DATE

10/31/01

END LEVEL

2.0120 IN

LEAK THRESHOLD

0.002 IN

TEST RESULT:

PASSED

INCON

INTELLIGENT CONTROLS INC.

P.O.. BOX 638

SACO ME 04072

1-800-984-6266

10/31/2001

11:58 AM

SUMP LEVEL REPORT

SUMP 1

2.012 IN

SUMP 2

7.201 IN

SUMP 3

3.218 IN

SELECT REPORT

SUMP

ALARM

M3

M4

M2

RIGHT

M1

LEFT

Pg 7

1.

2.

3.

Содержание TS-STS

Страница 1: ...Federal and State regulations for leak limit and test time requirements Recommendations for locating the TS STS console outside of the Class I Division 1 Group D Hazardous Areas during testing are based on NFPA 30 NFPA 30A and NFPA 70 NEC TS STS Sump Test System Quick Start Guide INCON P N 000 3004 Rev D Feb 2009 www fraklinfueling com This document may change without prior notice INCON is a Regis...

Страница 2: ... DISPENSOR SUMPS IN GROUPS SO OTHER DISPENSORS ARE LEFT IN SERVICE DURING TESTING GROUNDED 3 PRONG EXTENSION CORD REQ D SAFETY CONES DISPENSER 7 8 DISPENSER 5 6 Pg 2 SPLIT RING TS STS SUMP TEST SYSTEM SUMP TEST SYSTEM FLAT METAL ANGLE IRON REQUIRED TO SUSPEND PROBE SIDE VIEW TS STS STS PRB 12 LEAK TESTING PROBE WITH TSP SSP STAINLESS STEEL FLOAT DISPENSER SUMP WITH TEST SOLUTION Side View RECEPTAC...

Страница 3: ...TH TSP SSP STAINLESS STEEL FLOAT TURBINE SUMP WITH TEST SOLUTION Side View POWER CORD WITH A GROUNDED 3 PRONGED PLUG 3 RECEPTACLES FOR FOUR SCREW IN PROBE CABLE PLUGS 1 2 4 SUMP TAPE WEIGHT DOWN CABLE TO PREVENT ACCIDENTAL MOVEMENT DURING LEAK TESTING PROBE CABLE PN 600 0200 50 FEET Turbine Sump 2 TS STS SUMP TEST SYSTEM GROUNDED 3 PRONG EXTENSION CORD REQ D SAFETY CONES BUILDING SUMP TEST SYSTEM ...

Страница 4: ... left Use M2 to move the cursor to the right Use M4 to backspace delete text to the left of the cursor Follow the highlighted sequence at left to program the console Menus are in indented format lower levels to the right The setup program factory default settings are shown in ITALIC TEXT The console will auto exit the setup mode if no key is pressed after 3 minutes Minimum Setup Requirements 1 Fro...

Страница 5: ...r the Business Name LINE 2 LOCATION LINE 2 input 24 characters Max INTELLIGENT CONTROLS INC Enter other Business data LINE 3 LOCATION LINE 3 input 24 characters Max P O BOX 638 Enter the Street Address LINE 4 LOCATION LINE 4 input 24 characters Max SACO ME 04072 Enter the City and Zip code LINE 5 LOCATION LINE 5 input 24 characters Max 1 800 984 6266 Enter the Business Number NO SUMPS enter total ...

Страница 6: ...EEK Select the current day SUNDAY MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY 3 SYSTEM SUMP OKAY OKAY SYSTEM SUMP WARNING OKAY SYSTEM SUMP NO PAPER OKAY SYSTEM SUMP OKAY OKAY SYSTEM SUMP OKAY TEST LEVEL SUMP 1 SUMP 2 SUMP 3 SUMP 4 INCHES 2 01 3 09 1 76 3 12 SELECT FUNCTION 10 39 08 AM 10 29 2001 DISPLAY PRINTER SYSTEM SUMP OKAY LEAK Displays 1 Normal Display 2 Press the Check key to check th...

Страница 7: ...on demand from the keypad The Sump Leak Test and Alarm Reports print automatically The other reports such as the Sump Level Reports Alarm Reports and Sump Test Reports can be printed on demand Press the menu select keys and choose the type of report that you wish to printout Alarm reports will print as soon as an alarm is detected Leak test reports print automatically after the leak test is finish...

Страница 8: ...rt can be retrieved from the TS STS console through the communications port Comm Port 1 This port is located at the bottom side As with the printed reports this data is overwritten when a new test is run so it must be collected after each test The data can be stored in a database as opposed to saving the printouts For more information on this feature contact INCON Technical Service at 1 800 984 62...

Отзывы: