11
Num-
eric
Alpha-numeric
Protocol
Function:
Default
Value:
Programmable
Range:
OP 60 Aut27
Auto-Reset after “FA 27” Unstable
Synchro Signal Error (page 50)
OFF
On or OFF
OP 61
27rLY
Selects which relay will assert when the
“FA 27” error is active
OFF
OFF, LO, HI
OP 62 OtGLt
Sets On-Tap guard band limit (Degrees)
0.1
0.1 to 9999.9
OP 63 OtrLY
Selects which relay will assert when the
On-Tap guard band limit is reached
OFF
OFF, LO, HI
OP 64 OtdtE
On-Tap reference date
Enter day, month, year
01–01–00
OP 65 OtdIS
Scrolls through the list of taps, to select,
Press ENTER to display the highest
measured deviation, for that tap
Press MENU to escape back to the menu
Any
valid
tap
number
OP 66 Otdtd
Scrolls through the list of taps which have
exceeded the On-Tap alarm limit to select,
Press ENTER to display the highest
measured deviation, for that tap
Press MENU to escape back to the menu
Any
valid
tap
number
OP 67 OtCLr
Clears the On-Tap alarm
CL
OP 68 OtrSt
Resets all On-Tap logs & alarm
rESEt
OP 70 udCLt
Sets the alarm limit for the number of
changes
UP TO
any tap in
THOUSANDS
000.01
000.01 to 999.99
OP 71 udrLY
Selects which relay will assert when the
“UP TO” change alarm limit is reached
OFF
OFF, LO, HI
OP 72 uddtE
UP TO & DOWN TO Change counter
reference date Enter day, month, year
01–01–00
OP 73 uddIS
Scrolls through the list of taps to select,
Press ENTER to display the Change Up-
To count Press ENTER to display the
Change Down-To count, for that tap
Press MENU to escape back to the menu
0 Any
valid
tap
number
OP 74 udCLr
Clears an active Up-To and Down-To
Change alarm
CL
OP 75 udrSt
Resets all Change Up-To and Down-To
counters and alarm
rESEt
OP 80 POrt
Sets serial port parameters: (press the UP
or Down key to select a value, press the
enter key to move to the next parameter)
Baud rate
Word length
Parity (n=none, E=even, O=odd)
Stop bits
Address (for RS-485 Multi-drop)
9600
8
n
1
128
2400, 4800, 9600,
14400, 19200,
28800,38400,
57600, 76800
7 or 8
n, E, O
1 or 2
0 to 255
OP 85 PtnLt
Sets the limit for number of days without a
“Pass Thru Neutral”
OFF
Off, 0.1 to 365.0
OP 86 PtrLY
Selects which relay will assert when the
“Pass Thru Neutral” time limit is reached
OFF
OFF, LO, HI
OP 87 PtdIS
Displays the number of days since the last
“Pass-Through-Neutral”