impro IXP20 Скачать руководство пользователя страница 1

 

 

 

MODEL NUMBER:  

ISC920-0-0-GB-XX  
ISC921-5-0-GB-XX 

 

IXP20 C

ONTROLLER

 

ImproX IXP20 Controller                                                               

INSTALLATION MANUAL 

SPECIFICATIONS 

Working Environment 

Plastic Housing

 ............................ 

 

 

Designed to work in an indoor (dry) 
environment similar to IP40.  The Controller is 
not sealed against water. 

Power 

Input Voltage

 ................................ 

 

10 V DC to 30 V DC, polarity sensitive. 

Power Requirements (ISC920) 

Current (mA) 

Power (W) 

 

12 V DC with no peripherals 
connected and relays off ........  

75 

0.90 

 

24 V DC with no peripherals 
connected and relays off ........  

40 

0.96 

Power Requirements (ISC921) 

 

 

 

12 V DC with no peripherals 
connected and relays off ........  

130 

1.56 

 

24 V DC with no peripherals 
connected and relays off ........  

60 

1.44 

Relay Power Requirements

 ........ 

 

An additional ~0.4 W per Relay in use. 

Real Time Clock (RTC) Backup 
Battery 

 

 

Battery Type ...........................  

1 x 3 V, CR2032, Lithium cell Battery. 

 

Battery Life .............................  

1 year with power OFF,                                    
5 years with Power ON,                                       
5 years Storage with Battery Tab in place. 

Controller Communication 

Ethernet Port

 ................................ 

 

 

Standard Ethernet RJ45 connector. 
10/100 Base T, half or full duplex. 

 

 

 

Содержание IXP20

Страница 1: ...connected and relays off 75 0 90 24 V DC with no peripherals connected and relays off 40 0 96 Power Requirements ISC921 12 V DC with no peripherals connected and relays off 130 1 56 24 V DC with no p...

Страница 2: ...discipline Reader and Wiegand Readers The function is selectable via the DIP switches See Table 1 Power Output 12 V DC and 5 V DC selectable at maximum 200 mA Modes Supported Tag PIN code or Reason Co...

Страница 3: ...Input monitors a constant resistance through the circuit When the circuit is tampered with the Resistors are bypassed the Controller detects the resistance change raising an alarm Door Lock Type 2 Dry...

Страница 4: ...o a PC We do NOT however supply this cable with the Controller s accessories Find the following when unpacking the ImproX IXP20 Controller Either an ImproX IXP20 Twin Reader Controller with Web Interf...

Страница 5: ...with Impro Wiegand Readers use the 12 V power output option Note however that the Multi discipline Readers only connect using the 12 V power output option For maximum data communications distance inst...

Страница 6: ...ttery Tab 3 Pull the removable Battery Tab out of the Battery Holder 4 Immediately apply power to the Controller Replacement NOTE Because of the delicacy of this procedure we recommend you contact you...

Страница 7: ...tandard Wiegand Readers can only support one of two options HID Tags only or any other Tag type that is Slim Tags Omega Tags Mifare Standard Mifare Ultralite FeliCa Desfire WriTag 128 and WriTag 2048...

Страница 8: ...Button 3 of the ImproX QT Quad Transmitter reports 12 If the ImproX RF is connected then Button 4 of the ImproX QT Quad Transmitter reports Table 1 Reader 1 Select and Reader 2 Select DIP switch Sett...

Страница 9: ...he number to be a tag code The Controller discards the previously read Tag for the current one and the Controller will still expect a PIN code If the IXP20 Controller expects a Reason Code and receive...

Страница 10: ...ISC304 0 0 GB 06 April 2011 Page 10 ELECTRICAL CONNECTIONS Key Component Positions Figure 3 IXP20 Controller Key Component Positions...

Страница 11: ...C304 0 0 GB 06 April 2011 Page 11 Connecting the IXP20 Controller Figure 4 shows a typical electrical connection diagram for the IXP20 Controller Figure 4 Typical IXP20 Controller Electrical Connectio...

Страница 12: ...ISC304 0 0 GB 06 April 2011 Page 12 Figure 5 IXP20 Controller connected to Wiegand Reader...

Страница 13: ...ISC304 0 0 GB 06 April 2011 Page 13 Figure 6 IXP20 Controller connected to ImproX RF...

Страница 14: ...utomatically clears the System Database on the next restart 1 Remove the Controller s Front Cover Assembly 2 With power applied to the Controller toggle switch 1 of the Door Lock Select DIP switch ON...

Страница 15: ...e Terminals appear during the Software s Auto ID process MAC Address Figure 7 Sample MAC Address Label Each IXP20 Controller is supplied with a separate MAC Address Label much like the one shown in Fi...

Страница 16: ...ISC304 0 0 GB 06 April 2011 Page 16 Fixed Address Label Unique Location Description...

Страница 17: ...ISC304 0 0 GB 06 April 2011 Page 17 Fixed Address Label Unique Location Description...

Страница 18: ...ISC304 0 0 GB 06 April 2011 Page 18 Fixed Address Label Unique Location Description...

Страница 19: ...n Chart GUARANTEE OR WARRANTY CAUTION We reserve the right to nullify the products guarantee or warranty where you have not properly installed the Metal oxide Varistors This product conforms to our Gu...

Страница 20: ...to the ImproX IXP20 Controller ISC920 0 0 GB 03 and ISC921 5 0 GB 03 The last two digits of the Impro stock code indicate the issue status of the product ISC304 0 0 GB 06 Issue 07 Apr 2011 IXP20 Cont...

Отзывы: