ImproX O16 16 Channel Output Terminal         

INSTALLATION MANUAL

 

SPECIFICATIONS 

Working Environment

 ................. 

 

Mounted vertically, with the Cable Entry Glands 
at the lower side, the Terminal is designed to 
work in an indoor or outdoor environment 
similar to IP43.   

Input Voltage

 ................................ 

 

10 V DC to 30 V DC, polarity sensitive. 

Power Requirements

 

Current (mA)

 

Power (W)

 

 

Input Voltage 10 V DC 

 

Relays and Indicators all OFF  

35.40 

0.36 

 

Input Voltage 30 V DC 

 

Relays and Indicators all OFF 

16.50 

0.49 

 

Input Voltage 10 V DC 

 

Relays and Indicators all ON 

400 

 

Input Voltage 30 V DC 

 

Relays and Indicators all ON 

131 

3.90 

Relays 

 

 

Relay Output ..........................  

16 Relays, each with NO, COM and NC 
contacts. 

 

Relay Contact Ratings ...........  

1 A at 30 V DC. 
2 A at 125 V AC. 

Status Indicators 

 

 

Relay Status ...........................  

16 Red LEDs (On when Relay operates), 
(externally visible). 

 

Power Polarity Indicator .........  

Red LED (internally visible). 

 

Incoming RS485 Data ............  

Flashing Green LED (externally visible). 

 

Outgoing RS485 Data ............  

Flashing Red LED (externally visible). 

 

Unit Status .............................  

Red LED (Software controllable) (externally 
visible). 

Содержание IMPROX O16

Страница 1: ...OFF 35 40 0 36 Input Voltage 30 V DC Relays and Indicators all OFF 16 50 0 49 Input Voltage 10 V DC Relays and Indicators all ON 400 4 Input Voltage 30 V DC Relays and Indicators all ON 131 3 90 Relay...

Страница 2: ...en installing the Terminal Communications Distance The RS485 communications distance between the first ImproX Controller and the LAST ImproX unit in a cable run MUST NOT exceed 1 km 1 094 yd Achieve t...

Страница 3: ...Arc Suppression on the ImproX O16 Mounting the Terminal CAUTION Make certain that you mount the ImproX O16 on a vibration free surface Select the mounting position of the Terminal considering accessib...

Страница 4: ...T300 0 0 GB 02 July 2009 Page 4 ELECTRICAL CONNECTIONS Connecting the Terminal Figure 2 shows a detailed electrical connection diagram for the Terminal Figure 2 Typical ImproX O16 Electrical Connectio...

Страница 5: ...Address Label in the position of the Terminal on the sketched site plan When the system installation is complete and all the units are represented on the site plan by their Fixed Address Labels file...

Страница 6: ...XOT300 0 0 GB 02 July 2009 Page 6 USER NOTES...

Страница 7: ...XOT300 0 0 GB 02 July 2009 Page 7 USER NOTES...

Страница 8: ...icable to the ImproX O16 16 Channel Output Terminal XOT900 0 0 GB 00 The last two digits of the Impro stock code indicate the issue status of the product XOT300 0 0 GB 02 Issue 03 Jul 2009 ImproX O16...

Отзывы: