background image

Page 9

  9. CONDENSATION DRAIN LINE

  10. DEDICATED ELECTRIC RECEPTACLE

Insert the threaded drain adapter 

thru the bottom of the HRV/ERV and 

hand tighten the plastic nut, and with 

a wrench tighten the nut another half 

turn to assure a better seal.
Install the condensate line 

(included in drain kit). Insert 

condensate tubing by pushing 

clear plastic line over drain 

adapter. Make condensate trap 

by looping the clear plastic tubing. 

This procedure is to avoid foul odor 

to enter the HRV or ERV.

IMPORTANT: 

Always consult 

a certified technician to insure 

proper installation of main power.

NOTE:

 If LED light on the Duotrol 

remains green, motors not 

energized controls do not operate. 

Polarization in main AC outlet are 

inverted.
It is recommended that the HRV/

ERV have a dedicated receptacle 

with 115v. It is not recommended to 

connect unit with an extension cord.

figure 10.1 Insert the power cord on top of the unit. Press 

firmly

 to 

make sure the power cord is secure.

figure 10.2 It is recommended that the HRV or ERV have a dedicated 

receptacle with 115v. It is not recommended to connect unit with 

an extension cord.  If no receptacle is available please call an 

electrical contractor and have one installed. Insure polarized is 

correct

figure 9.1 Make a loop in condensate line, not be subject to  

freezing temperatures.

figure 9.2 Use a condensate pump if you don’t have access to a drain.

  11. OUTSIDE FRESH AIR AND EXHAUST AIR HOODS

TIP TO INSTALLER

: We recommend 

and it is 

good practice

 to have a 

minimum of 6ft (1.83 m) between 

the supply and exhaust vents, 

unless using a concentric vent 

design to prevent contamination of 

intake air.
Always properly seal the supply 

& exhaust hoods to the exterior 

of the thermal envelope of the 

building with caulk or other similar 

material to inhibit air leakage.

NOTE: 

Outdoor air intake hoods shall 

be located to avoid contamination 

from sources such as:
• Exhaust air openings
• Driveways (auto exhaust)
• Combustion appliances
• Gas meters, oil fill pipes
• Garbage containers
• Attics or crawl spaces
• Under  deck  or  other  areas  of 

questionable air quality

figure 11.1 Locating Outside Hoods

6ft (1.83 m)

18" (457 mm)

IMPORTANT:

 Always consult your national and 

local regulations, building and safety codes.

Содержание PH 10.22 HRV ES

Страница 1: ...n order to offer at all times quality products that are highly competitive Imperial Air Technologies 480 Ferdinand Blvd Dieppe NB E1A 6V9 1 888 724 5211 Fax 506 388 4633 www imperialgroup ca RESIDENTI...

Страница 2: ...ation requirements 3 2 Fitting equivalent lengths 4 3 Types of Installations 5 4 Installation Kit 7 5 Finding a suitable installation area for HRV or ERV 7 6 Installation of the HRV ERV 7 7 Insulated...

Страница 3: ...CFM L S CFM REQUIRED Master Bedroom x 20 cfm 10 L s With Basement x 20 cfm 10 L s Single Bedroom x 10 cfm 5 L s Living Room x 10 cfm 5 L s Dinning Room x 10 cfm 5 L s Family Room x 10 cfm 5 L s Recre...

Страница 4: ...t length 35 ft 10 7 m Round plastic diffuser equivalent length 100 ft 30 5 m NOTE Maximum airflow assumes diffuser is in full open position Tee take off equivalent length 50 ft 15 24 m Angle boot equi...

Страница 5: ...or the forced air system s manufacturer The HRV and forced air system must be in continuous mode to achieve maximum comfort and to avoid cross contamination NOTE TO INSTALLER Dwellings with multiple f...

Страница 6: ...oved tools and material Also use steel duct connections for these type of installs hen Distribution to living space A B A B Not less than 10ft 3 m HRV ERV Distribution to living space 18 457 cm 6 ft 1...

Страница 7: ...separate circuit breaker is also recommended You should have access to a condensate drain near the HRV ERV to avoid the use of condensate pump 6 INSTALLATION OF THE HRV ERV The entire line of Imperia...

Страница 8: ...ct with the collar before securing over the four hooks The Fresh air from outside and the Exhaust air to outside from the termination ducts to the HRV ERV must be fully insulated of thermal insulation...

Страница 9: ...RV have a dedicated receptacle with 115v It is not recommended to connect unit with an extension cord If no receptacle is available please call an electrical contractor and have one installed Insure p...

Страница 10: ...aust air to outside AIRFLOW INSTALLATION IMPORTANT Install ventilation hood a minimum of 18 457mm above grade Do not install under a deck enclose porch patio garages crawl spaces or attics WARNING Ins...

Страница 11: ...position will allow you to adjust the cfm on both motors proportionately if necessary Step 7 Once this is completed you have set the high speed on your HRV ERV To exit the balancing mode you must pres...

Страница 12: ...NNECTION RD 1 2 wires RD 3D RD 4D 4 wires XDH Series only R G B W G R B G R R W B G To Casing Screw for Ground Jumper JP 4 2 Relays 1 Relay LVC Version 1 LVC Version 2 Jumper JP 4 R G B W G R B G R R...

Страница 13: ...e Alternate Forced Air Wiring LOCATING THE WIRING DIAGRAM NOTE TO INSTALLER Wiring Diagram for the entire line of HRV ERV Models are placed on the back of each Exhaust motor bracket CAUTION Thermostat...

Страница 14: ...ll bracket is used for hanging the units Verify that flexible duct connections are use between the HRV or ERV and the rigid duct Verify that the motors are operating and are not obscured by any debris...

Страница 15: ...vers Ref Fig 17 1 for proper orientation of louvers Twice a year and clean it as required consult your owner s manual for instructions on inspecting and cleaning the core A build up of dust and dirt c...

Страница 16: ...Imperial Air Technologies 480 Ferdinand Blvd Dieppe NB E1A 6V9 1 888 724 5211 Fax 506 388 4633 www imperialgroup ca Item PR0754...

Отзывы: