background image

INTRODUCTION

The LD900 features a long life solid electrolyte sensor technology that is designed 
to detect more current and difficult HFC refrigerants such as R-134a, R-410A, 
R-404A, R-407A, and R-507 in addition to the new HFO-1234yf and all HCFC (R-
22) and CFC (R-12) refrigerants including SNAP approved hydrocarbon blends. 

Our unique digital leak size indicator takes the guesswork out of whether to repair 
a small leak. The digital display is independent from the audio alarm and sensitivity 
level, allowing the precise pinpointing of the leak source. 

The LD900 does not require rechargeable batteries. 

FEATURES

•  Unique numeric leak size indicator
•  Long life, stable sensor
•  R-134a sensitivity .05 oz/yr 
•  R-1234yf sensitivity .015 oz/yr
•  R-22 sensitivity .025 oz/yr
•  Design certified to meet SAE J2791, SAE J2913, European EN14624 
•  Automatic calibration and reset to ambient 
•  Visual LED leak alarm near sensor 
•  3 adjustable sensitivity levels
•  Low battery indicator 
•  True mechanical pump
•  Audio mute function 
•  Uses 4 AA alkaline batteries
•  CE Certified 
•  Comfortable Sanoprene grip
•  2-year warranty includes sensor 
•  Made in USA

OPERATING INSTRUCTIONS

1. TURN  ON:

 Press the ON/OFF button once to turn on and again to turn off. 

NOTE: Hold button down for approximately 1 second to turn unit off. 

2. WARM  UP:

 

The detector automatically starts heating the sensor. During the 

heating cycle, the digital leak size indicator will flash 0 and the detector will sound 
a slow “beep”. Warm up time is usually less than 20 seconds.

3. READY:

 The detector is ready to begin searching for leaks when the flashing 

0 stops and the green sensitivity LED turns on. The audio “beep” increases in 
frequency and the probe LED begins to blink steadily.

4. SEARCHING:

 When searching for leaks, move the sensor tip along A/C lines 

and fittings no further away than 0.4 in. (9.5 mm) and no faster than 3 in./sec. (75 
mm/sec.) If the detector alarms, make smaller sweeps back and forth until the leak 
source can be pin pointed. NOTE: The LD900 only responds to changes in leak 
concentration. The alarm will re-set automatically if the sensor tip is held at the leak 
source. If the leak detector has been out of use for an extended period, weeks or 
months, the following action is recommended. Power on the instrument and allow it 
to come out of warm up. Then run it with the sensitivity level in the Hi (high) position 
for several minutes before testing it with the Leak Test Vial. This action will guarantee 
that the sensor is fully conditioned for maximum response to refrigerant gas. 

Digital Leak Size Indicator

Low Battery Indicator
Sensitivity Level Indicators
Audio Mute & Sensitivity Level Selectors
Power On/Off

LD900 CONTROL PANEL

2

3

LeakDetectors-LD900-UserManual.indd   2-3

12/7/16   1:08 PM

Отзывы: