ImmersionRC | ImmersionRC RF Power Meter
1
ImmersionRC RF Power Meter
Operator’s Manual
October 2013 Edition, Preliminary
Страница 1: ...ImmersionRC ImmersionRC RF Power Meter 1 ImmersionRC RF Power Meter Operator s Manual October 2013 Edition Preliminary...
Страница 2: ...power combinations Standard high quality SMA connector Un attenuated VSWR 1 5 1 below 1GHz 1 7 1 1GHz 8GHz Attenuated VSWR 1 05 1 below 1GHz 1 5 1 1GHz 8GHz typical o Note that the Attenuated VSWR de...
Страница 3: ...Since SMA connectors are easily damaged by repeated connection disconnection it is recommended to connect the attenuator directly to the power meter and use the SMA adapter to connect to the RF sourc...
Страница 4: ...the total attenuation e g 10dB 10dB 20dB of attenuation If calibration data for the attenuator is available use the Fine Attenuation control also NOTE If the Pwr value is flashing the measured power i...
Страница 5: ...ge mode not Peak and attenuator setting at 0dB Screw the first of the whips to be compared onto it vertically same polarization as the transmitter and place it on another tripod Adjust the distance be...
Страница 6: ...ect the appropriate frequency range using the left right buttons and apply power to the meter and the device under test Example 3 Measuring A V Tx output power Connect the output of the device to be t...