
32
INS
TALLER
U
SER
M
AINTEN
AN
CE
TECHNI
CI
AN
TECHNI
CAL
D
AT
A
1.19 C9 ADAPTOR KIT INSTALLATION
This kit allows an Immergas boiler to be installed in "C
93
" configuration, with combustion air intake directly from the shaft where the flue
gas exhaust is, obtained by means of a ducting system.
System composition
The system must be combined with the following components (sold separately) to be functional and complete:
- kit C
93
Ø 100 or Ø 125 version;
- rigid ducting Ø 60 and Ø 80 and flexible Ø 50 and Ø 80 kit;
- flue exhaust kit Ø 60/100 or Ø 80/125 configured according to the installation and type of boiler.
Mounting the C
9
adapter kit (Fig. 26)
(Version Ø 125 only) before assembly check the gaskets are in the right position.
In the event component lubrication (already carried out by the manufacturer) is not sufficient, remove the residual lubricant
using a dry cloth, then to ease fitting coat the parts with common or industrial talc.
To favour the removal of possible condensate forming in the exhaust pipe, tilt the pipes towards the boiler with a minimum
slope of 1.5% (Fig. 24)
1. Mount the components of kit "C
9
" on the door (A) of the ducting system (Fig. 26).
2. (Version Ø 125 only) mount the flanged adaptor (11) interposing the concentric gasket (10) on the boiler, fitting it with the screws (12).
3. Mount the ducting system as described in the relative instructions sheet.
4. Calculate the distances between the boiler drain and the bend of the ducting system.
5. Prepare the boiler flue system, making sure that the internal pipe of the concentric kit is fitted up to the end stop in the ducting system
curve (Quota "X" Fig. 27), whereas the external pipe must reach the end stop of the adapter (1).
6. Mount the cover (A) complete with adaptor (1) and caps (6) on the wall.
7. Assemble the flue system to the ducting system.
Once all components have been assembled properly, the exhaust flue gas will be expelled via the ducting system; the combustion air for
normal boiler operation will be aspirated directly by the shaft (Fig. 27).
C
83
C
S
A
24
Key (Fig. 24):
A - Intake
C
- Minimum gradient 1.5
%
S - Exhaust
Содержание VICTRIX ZEUS SUPERIOR 25
Страница 34: ...34 Installer User Maintenance technician Technical Data C93 X 27 ...
Страница 127: ...127 ...