3.4  CONVERTING THE BOILER TO 

OTHER TYPES OF GAS.

If the boiler has to be converted to a different 

gas type to that specified on the data nameplate, 

request the relative conversion kit for quick and 

easy conversion.

The gas conversion operation must be carried 

out by an authorised company (e.g. Authorised 

Technical After-Sales Service).

To convert to another type of gas the following 

operations are required:

- remove the voltage from the appliance;
-  replace the main burner injectors, making sure 

to insert the special seal rings supplied in the 

kit, between the gas manifold and the injectors;

- apply voltage to the appliance;
- select, using the boiler key, the gas parameter 

type (P01) and select (

nG

) in the case of meth-

ane or propane air supply or (

LG

) in the case 

of LPG supply and save it;

- adjust the boiler nominal heat output;
- adjust the boiler nominal heat output in do-

mestic hot water phase;

-  adjust the boiler nominal heat output in heating 

phase (para. 3.7);

- adjust (eventually) the maximum heating 

power (para. 3.7);

- seal the gas flow rate devices (if adjusted);
-  after completing conversion, apply the sticker, 

present in the conversion kit, near the da-

ta-plate. Using an indelible marker pen, delete 

the data relative to the old type of gas.

These adjustments must be made with reference 

to the type of gas used, following that given in 

the table (

Par. 3.17

).

3.5  CHECKS FOLLOWING 

CONVERSION TO ANOTHER TYPE 

OF GAS.

After making sure that conversion was carried 

out with a nozzle of suitable diameter for the 

type of gas used and the settings are made at the 

correct pressure, check that:

- there is no flame in the combustion chamber;
-  the burner flame is not too high or low and that 

it is stable (does not detach from burner);

- the pressure testers used for calibration are 

perfectly closed and there are no leaks from 

the gas circuit.

N.B.:

 all boiler adjustment operations must be 

carried out by a qualified company (e.g. Author-

ised After-Sales Assistance). Burner adjustment 

must be carried out using a differential "U" or 

digital type pressure gauge connected to the 

gas valve outlet pressure point (

part. 4

 

Fig. 14

), 

keeping to the pressure value given in the table 

(

Par. 3.17

) according to the type of gas for which 

the boiler is prepared.

3.6  POSSIBLE ADJUSTMENTS.

• Adjustment of boiler nominal thermal heat 

output.

- Activate the chimney sweep function.  

(

Ref. Par. 3.9

) in DHW, making sure that the 

maximum boiler output is reached (on the 

display “99” is to be displayed).

- From the brass nut (

Part.

 

3 Fig. 14

) adjust the 

boiler nominal output, observing the maxi-

mum pressure values stated in the tables (

Par. 

3.17

) depending on the type of gas.

-  By turning in a clockwise direction the heating 

potential increases and in an anti-clockwise 

direction it decreases.

• Adjust the boiler minimum heat output in the 

domestic hot water phase (

Part. 2 Fig. 14

).

 

N.B.:

 only proceed after having calibrated the 

nominal pressure.

  Adjustment of the minimum thermal input 

is obtained by operating on the cross plastic 

screws (2) on the gas valve maintaining the 

brass nut blocked (3);

- press the button 4 (

Fig. 10

) up to reach the 

minimum boiler output (on the display “00” 

is to be displayed). The pressure to which the 

boiler minimum power must be adjusted, must 

not be lower than that stated in the tables (

par. 

3.17

) depending on the type of gas.

NOTE: 

to adjust the gas valve, remove the plastic 

cap (6); after adjusting, refit the cap.
•  Adjustment of the boiler minimum heat output 

in heating phase.

 

NOTE:

 only proceed after having calibrated 

the minimum domestic hot water pressure.

  To adjust the minimum heat output during the 

heating phase, change parameter (5), increasing 

the value the pressure increases, reducing it the 

pressure drops.

-  The pressure to which the boiler minimum heat 

output must be adjusted, must not be lower 

than that stated in the tables (

Par. 3.17

).

Key:

  1 -  Coil

  2  -  Minimum output adjustment 

screws

  3  -  Maximum output adjust-

ment nut

  4  -  Outlet pressure point  

gas valve

  5  -  Gas valve inlet pressure point

  6  -  Protection hood

VK 8105 M GAS valve

Содержание NIKE STAR 24

Страница 1: ...pe B and natural draught The European regulation 813 2013 provides that this boiler can be installed only to replace similar equipment connected to existing branched multiple flues IE Instructions and warning book Installer User Maintenance technician 1 040577ENG ...

Страница 2: ......

Страница 3: ...safety in the work site environment protection injury prevention it is necessary to comply with the provisions specified in the regulations in force and principles of good technique In compliance with the legislation in force the systems must be designed by qualified professionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with...

Страница 4: ...re central heating system pressure 15 2 9 Draining the system 15 2 10Antifreeze protection 15 2 11Case cleaning 15 2 12Decommissioning 15 3 Commissioning the boiler initial check 16 3 1 Hydraulic Diagram 16 3 2 Wiring diagram 17 3 3 Troubleshooting 18 3 4 Converting the boiler to other types of gas 19 3 5 Checks following conversion to another type of gas 19 3 6 Possible adjustments 19 3 7 Program...

Страница 5: ...ained staff and original spare parts Do not attempt to modify or repair the appliance alone Failuretocomplywiththeaboveimpliespersonal responsibility and invalidates the warranty Installation Standards installation of these boilers in bedrooms studio flats and bathrooms or in premises where there are wood fired heaters or solid fuel heaters in general and in premises next to or connected to them i...

Страница 6: ...7 2002 or local standards in force The materials used for the central heating circuit of Immergas boilers withstand ethylene and propyl ene glycol based antifreeze liquids if the mixtures are prepared perfectly For life and possible disposal follow the suppli er s instructions Protect the domestic hot water circuit against freezing by using an accessory that is supplied on request antifreeze kit c...

Страница 7: ...er specifi cations as shown on the boiler data nameplate Boilers are supplied complete with a Y type power cable The power supply cable must be connected to a 230V 10 50Hz mains supply respecting L N polarity and earth connection this network must also have a multi pole circuit breakerwithclassIIIovervoltagecategory When replacing the power supply cable contact a qualified firm e g the Authorised ...

Страница 8: ...rated In the case of repeated interventions of the fumes exhaust control device check the fumes exhaust flue and the ventilation of the room in which the boiler is located For the right functioning of the Nike Star the pipe the boiler is connected to is to have a mini mum vacuum equivalent to the fan assisted of 1 meter of vertical pipe with a diameter of 130 mm 1 12 SYSTEM FILLING Once the boiler...

Страница 9: ... mode it is sufficient to press button 1 once To change operation mode press the button for between 2 to 10 seconds until the current config uration flashing each time the button is pressed all possible functions are scrolled cyclically After a few seconds without doing any operation the circulator memorises the selected mode and goes back to operation display Attention The circulator has various ...

Страница 10: ...rculator continues operating low power supply voltage Voltage off range Check power supply R Y Y Y Y On Off On Off Off Electrical fault Circulator pump blocked The circulator is locked due to power supply too low or serious malfunction Check the power supply if the anomaly persists replace the circulator Key 1 Function selection button 2 Green G red R LED 3 4 yellow LEDs Y Head available to the sy...

Страница 11: ...larly useful for maintenance as it allows to drain just the boiler without having to empty the entire system Polyphosphate dispenser kit The polyphos phate dispenser reduces the formation of lime scale and preserves the original heat exchange and domestic hot water production conditions The boiler is prepared for application of the polyphosphate dispenser kit Connection unit kit It includes pipes ...

Страница 12: ...nce It is prohibited and dangerous to obstruct the air intake even partially for the ventilation of the room in which the boiler is installed Due to the danger operation is also prohibited in the same room as suction devices or the like at the same time as the boiler unless there are additional openings dimensioned in a way to satisfy the additional requirement for air For the dimensioning of thes...

Страница 13: ...owed resets already performed Attention the anomaly can be reset 5 times consecutively after which the function in inhibited for at least one hour One attempt is gained every hour for a maximum of 5 attempts By switching the appliance on and off the 5 attempts are re acquired 10 Insufficient system pressure Water pressure inside the central heating circuit that is sufficient to guarantee the corre...

Страница 14: ...ximum no of software errors The maximum number of software errors possible has been reached Press the Reset button 1 1 If the shutdown or fault persists contact an authorised company e g Authorised Technical After Sales Service 2 6 INFORMATION MENU Pressing the buttons 3 and 4 simultaneously for 3 seconds the Information menu is acti vated which displays some boiler functioning parameters Press bu...

Страница 15: ... the boiler falls below 4 C standard protection up to the min temperature of 5 C and stops once it ex ceeds 42 C The antifreeze function is guaranteed if the boiler is fully operative and not in block status and is electrically powered To avoid keep ing the system switched on in case of a prolonged absence the system must be drained completely or antifreeze substances must be added to the heating ...

Страница 16: ... a draught gauge positioned at the exit of the appliance combustion products check that there is no backflow of combustion products into the room even during function ing of fans ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified ensure production of domestic hot water ensure sealing efficiency of water circuits check ventilation and or a...

Страница 17: ...erature S23 Key to increase central heating temperature S24 Key to decrease central heating temperature T1 Ignition transformer T2 Boiler P C B transformer X40 Room thermostat jumper Y1 Gas valve Y2 Gas valve modulator 1 User interface 2 N B The user interface is on the welding side of the boiler board 3 230 Vac 50Hz supply voltage 4 The X5 connector is used for automatic inspection Comando Amico ...

Страница 18: ...excessively low In this case make the boiler run at higher temperatures Frequent interventions of the chimney safety thermostat This can be caused by obstructions in the fumes circuit Check the flue The flue may be obstructed or by height or section not suitable for the boiler Ventilation may be insufficient see room ventilation point Presence of air in the system Check opening of the special air ...

Страница 19: ...st be carried out by a qualified company e g Author ised After Sales Assistance Burner adjustment must be carried out using a differential U or digital type pressure gauge connected to the gas valve outlet pressure point part 4 Fig 14 keeping to the pressure value given in the table Par 3 17 according to the type of gas for which the boiler is prepared 3 6 POSSIBLE ADJUSTMENTS Adjustment of boiler...

Страница 20: ...ed thermostatic valves etc it may be neces sary to delay ignition 00 20 00 3 seconds 01 30 seconds 02 60 seconds 20 600 sec onds 00 P03 Function anti leakage This function reduces the heating temperature to 57 C in the case that domestic hot water circulation is detected in the heating mode on oF oF P04 Domestic hot water post circu lation function With the post circulation function active after d...

Страница 21: ...This function allows the technician to check the combustion parameters After the checks disable the function switching the boiler off and then on again or simply by pressing the reset button for about 5 seconds Part 1 Fig 10 The heating power can be set to P06 and P05 by pressing buttons 3 or 4 The power can be changed by one percentage point by pressing buttons 5 or 6 If you wish to run the chimn...

Страница 22: ...5 byunscrewing the two screws 6 by pulling towards yourself and to the bottom to release it from the two slots available on the bottom of the casing Remove the plugs from the cover 1 by pulling them to you as shown by the arrows Undo the 2 front screws 2 and the 2 lower screws 3 which fasten the casing 4 Pull the casing 4 towards yourself and up at the same time to detach it from the upper hooks ...

Страница 23: ...ion vessel load is at 1 0 bar Check that the system static pressure with system cold and after refilling the system by means of the filling valve is between 1 and 1 2 bar Check visually that the safety and control devices have not been tampered with and or shorted in particular temperature safety thermostat water pressure switch flue gas control thermostat Check the condition and integrity of the ...

Страница 24: ... Hot water production useful heat output kW kcal h 23 6 20296 Domestic hot water adjustable temperature C 35 55 Domestic hot water circuit min pressure dynamic bar 0 3 Domestic hot water circuit max operating pressure bar 10 Minimum D H W flow rate l min 2 0 Flow rate capacity in continuous duty T 30 C l min 11 1 Weight of full boiler kg 25 3 Weight of empty boiler kg 24 6 Electrical connection V ...

Страница 25: ...odel code Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat input Pn min Minimum heat output Pn max Maximum heat output PMS Maximum system pressure PMW Maximum domestic hot water pressure D Specific flow rate TM Maximum operating temperature NOx Cl...

Страница 26: ...d elmin 0 014 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 003 kW Emissions of nitrogen oxides NOX 138 mg kWh For mixed central heating appliances Stated load profile XL Domestic hot water production efficiency ηWH 78 Daily electrical power consumption Qelec 0 119 kWh Daily gas consumption Qfuel 25 631 kWh Contact information IMMERGAS EUROPE S r o PRIEMYSELNA ULICA 478...

Страница 27: ... installation since such efficiency is affected by additional factors such as the heat loss in the distribution system and the size of the products compared to the size and features of the building Seasonal central heating energy efficiency of the set Seasonal central heating energy efficiency class of the set Solar contribution From the board of the solar device Class I 1 Class II 2 Class III 1 5...

Страница 28: ... this sheet may not reflect the actual energy efficiency after installation since such efficiency is affected by additional factors such as the heat loss in the distribution system and the size of the products compared to the size and features of the building Seasonal central heating energy efficiency of the set Seasonal central heating energy efficiency class of the set Solar contribution From th...

Страница 29: ...I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy efficiency of the set of products indicated in this sheet may not reflect the actual energy efficiency after installation since such efficiency is affected by additional factors ...

Страница 30: ... 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy efficiency of the set of products indicated in this sheet may not reflect the actual energy efficiency after installation since such efficiency is affected by additional factors such as the heat loss in the distribution system and the size of the products compared to...

Страница 31: ......

Страница 32: ...as com Immergas Europe S r o 05951 Poprad Matejovce SK Tel 421 524314311 Fax 421 524314316 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 040577ENG rev ST 002996 001 11 17 Inglese per IRLANDA IE ...

Отзывы: