background image

20

INS

TALLER

US

ER

 MAINTEN

AN

CE TECHNI

CI

AN

2.4  USING THE BOILER.

Before ignition make sure the heating system 

is filled with water and that the manometer (7) 

indicates a pressure of 1 ÷ 1.2 bar.

- Open the gas cock upstream from the boiler.
- Press the button (2) until the display switches 

on, after which press the button in sequence 

(2) and take the boiler to the summer (

or winter (

) position.

• 

Summer 

(

)

in this mode the boiler 

functions only to produce the DHW, the 

temperature is set via the buttons (3-4) and the 

relative temperature is shown on the display via 

the indicator (16).

• Winter 

(

)

:

 in this mode the boiler functions 

both for producing domestic hot water and 

heating the environment. The temperature of 

the DHW is always regulated via buttons (3-4), 

the heating temperature is regulated via buttons 

(5-6) and the relative temperature is shown on 

the display via the indicator (16).

From this moment the boiler functions 

automatically. With no demand for heat (heating 

or domestic hot water production) the boiler 

goes to “standby” function, equivalent to the 

boiler being powered without presence of flame. 

Each time the burner ignites, the relative flame 

present symbol is displayed (10) with relative 

output scale.
• 

Operation with Comando Amico Remoto

V2

 

(CAR

V2

) (Optional)

. If the CAR

V2

 is connected, 

the (

) symbol will appear on the display. 

The boiler regulation parameters can be set 

via the CAR

V2

 control panel and the reset 

button (1) remains active on the boiler control 

panel, along with the switch-off button (2) 

(“off” mode only) and the display where the 

functioning state is shown.

 

Attention:

 if the boiler is put into "off" mode, 

the “ERR>CM” connection error symbol 

will appear on the CARCAR

V2

. The CAR

V2

 is 

however powered constantly so as not to loose 

memorised programs.

• 

Operation with optional external probe 

(

)

.

 In the case of a system with optional 

external probe, the boiler flow temperature 

for room central heating is managed by the 

external probe depending on the external 

temperature measured (Par. 1.6). The flow 

temperature can be modified by selecting 

the functioning curve via buttons (5 and 6), 

selecting a value from "0 to 9" (Fig. 1-6).

  With external probe present, the relative 

symbol (12) will appear on the display. In the 

central heating phase, if the temperature of the 

water contained in the system is sufficient to 

heat the radiators, the boiler can only function 

with the activation of the pump.

• 

“Stand-by” mode.

 Press button (2) in 

succession until the (

) symbol appears. 

The boiler remains active from this moment 

and the anti-freeze function, pump anti-block 

function and 3-way and signalling of any 

anomalies is guaranteed.

 

N.B.:

 in these conditions the boiler is 

considered still powered.

• 

“Off” mode.

 By holding the button (2) down 

for 8 seconds, the display switches-off and the 

boiler is off completely. The safety functions are 

not guaranteed in this mode.

 

N.B.:

 in these conditions the boiler is considered 

still live even if there are no functions active.

• 

Display functioning.

 The display lights up 

during the use of the control panel, after 15 

seconds inactivity, the brightness drops until 

just the active symbols are displayed. The 

lighting mode can be varied via parameter P2 

in the circuit board customisation menu.

2.5  FAULT AND ANOMALY SIGNALS.

The boiler signals out anomalies by flashing on 

the display and relative error codes, listed on the 

table, are displayed.

Anomaly signalled

code

displayed

(flashing)

No ignition block

01

Safety thermostat block 

(overheating), flame control 

anomaly

02

Fan anomaly

03

Generic boiler P.C.B. anomaly

04

Flow probe anomaly

05

Domestic hot water probe 

anomaly

06

Maximum N° of reset

08

Insufficient system pressure

10

Flue pressure switch failure

11

Configuration error

15

Parasite flame

20

Push button control panel 

anomaly

24

Insufficient circulation

27

Loss of remote control 

communication.

31

Low power supply voltage

37

Loss of flame signal

38

Block due to loss of 

continuous flame signal

43

Attention: 

the Anomaly can be reset 5 times 

consecutively, after which the function in 

inhibited for at least one hour. One attempt is 

gained every hour for a maximum of 5 attempts. 

By switching the appliance on and off the 5 

attempts are re-acquired.

Ignition block.

 The boiler ignites automatically 

with each demand for room heating or hot 

water production. If this does not occur within 

10 seconds, the boiler goes into ignition block 

(code 01). To eliminate “ignition block” the Reset 

button (1) must be pressed. On commissioning 

or after extended downtime, it may be 

necessary to eliminate the “ignition block”. If 

this phenomenon occurs frequently, contact a 

qualified technician for assistance (e.g. Immergas 

After-Sales Technical Assistance Service).

Overheating thermostat block.

 During normal 

functioning, if a fault causes excessive overheating 

internally, the boiler goes into overheating block 

(code 02). After allowing to cool, eliminate the 

"overtemperature block" by pressing the Reset 

key (1). If this phenomenon occurs frequently, 

contact a qualified technician for assistance 

(e.g. Immergas After-Sales Technical Assistance 

Service).

Fan anomaly.

 This occurs if the fan is blocked 

or if the intake or drain pipes are obstructed. If 

normal conditions are restored the boiler restarts 

without having to be reset. If this anomaly 

persists, contact a qualified technician for 

assistance (e.g. Immergas After-Sales Service).

Generic boiler P.C.B. anomaly.

 This happens 

when a signal is incorrectly recognised by 

the boiler P.C.B. microprocessor (code 04). 

To eliminate “boiler P.C.B. generic anomaly 

block” the Reset button (1) must be pressed. If 

this phenomenon occurs frequently, contact a 

qualified technician for assistance (e.g. Immergas 

After-Sales Technical Assistance Service).

Delivery probe anomaly.

 If the board detects 

an anomaly on the delivery probe (code 05), 

the boiler will not start; contact a qualified 

technician for assistance (e.g. Immergas After-

Sales Technical Assistance Service).

Domestic hot water probe anomaly.

 If the board 

detects an anomaly on the domestic hot water 

NTC probe, the boiler signals the anomaly. In this 

case the boiler continues to produce domestic 

hot water but not with optimal performance. 

Moreover, the DHW anti-freeze function is 

prevented and an authorised technician must 

be called (e.g. Immergas After-Sales Service).

Maximum N° of reset.

 Number of allowed resets 

that have already been used. 

Insufficient system pressure. 

Water pressure 

inside the heating system (code 10), sufficient to 

guarantee the correct functioning of the boiler, 

is not detected. Check that the system pressure 

is between 1÷1.2 bar.

Flue gas pressure switch failure.

 It occurs in 

the case of an error on the circuit board that 

gives consent for fan start-up incorrectly or 

in the case of flue-gas pressure switch fault 

(code 11). If normal conditions are restored the 

boiler restarts without having to be reset. If this 

anomaly persists, contact a qualified technician 

for assistance (e.g. Immergas After-Sales Service).

Configuration error.

 If the board detects an 

anomaly or incongruency on the electric wiring, 

the boiler will not start. If normal conditions are 

restored the boiler restarts without having to be 

reset. If this anomaly persists, contact a qualified 

technician for assistance (e.g. Immergas After-

Sales Service).

Parasite flame.

 This occurs in case of a leak on 

the detection circuit or anomaly in the flame 

control unit.(code 20), try to reset the boiler. 

If the anomlay continues contact a qualfied 

technician (e.g. Immergas After-Sales Technical 

Assistance Service).

Push button control panel anomaly.

 This occurs 

when the P.C.B. detects an anomaly on the push 

button control panel. If normal conditions are 

restored the boiler restarts without having to be 

reset. If this anomaly persists, contact a qualified 

technician for assistance (e.g. Immergas After-

Sales Service).

Содержание Mini Eolo 24 3 E

Страница 1: ...MINI EOLO 24 3E Instruction and warning book IE 1 038773ENG ...

Страница 2: ......

Страница 3: ... installing the Immergas kit As for the other issues related to boiler installation e g safety in the work site environment protection injury prevention it is necessary to comply with the provisions specified in the current regulation and technical standards In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established by ...

Страница 4: ...al warnings 19 2 3 Control panel 19 2 4 Using the boiler 20 2 5 Fault and anomaly signals 20 2 6 Boiler shutdown 21 2 7 Restore heating system pressure 21 2 8 Draining the system 21 2 9 Anti freeze protection 21 2 10 Case cleaning 21 2 11 Decommissioning 21 3 Commissioning the boiler initial check 22 3 1 Hydraulic Diagram 22 3 2 Wiring diagram 23 3 3 Troubleshooting 23 3 4 Information Menu 24 3 5 ...

Страница 5: ...s plastic polystyrene etc Do not place household appliances underneath the boiler as they could be damaged if the safety valve intervenes with obstructed conveying system the safety valve must be conveyed away by a draining funnel or if there are leaks from the hydraulic connections on the contrary the manufacturer cannot be held responsible for any damage caused to the household appliances For th...

Страница 6: ...uit from freezingbyintroducingatopqualityanti freeze liquid into this circuit which is not noxious to health The instructions of the manufacturer of this liquid must be followed scrupulously regarding the percentage necessary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential pollution class of water 2 The materials used for the...

Страница 7: ...fully clean the heating system pipes radiators etc with special pickling or de scaling products to remove any deposits that could compromise correct boiler operation A chemical treatment of the thermal system water is required in compliance with the technical standards in force in order to protect the system and the appliance from deposits e g lime scale slurry or other hazardous deposits Water co...

Страница 8: ...or the transmission of data between boiler and chrono thermostat Comando Amico Remoto Remote ControlV2 or On Off chrono thermostat electrical connections Optional The operations described below must be performed after having removed the voltage from the appliance Any thermostat or On Off environment chrono thermostat must be connected to clamps 40 and 41 eliminating jumper X40 Fig 3 2 Make sure th...

Страница 9: ...ng and joining of the elements correctly Attention if the exhaust terminal and or extension concentric pipe needs shortening consider that the internal duct must always protrude by 5 mm with respect to the external duct Diaphragm installation Attention based on the boiler model checking which type of fan is installed use appropriate diaphragms For correct functioning of the boiler it is necessary ...

Страница 10: ...6 Exhaust m 2 0 Terminal complete with intake exhaust vertical concentric Ø 80 125 Intake and Exhaust 33 m 2 0 m 5 5 Intake m 14 3 Exhaust m 11 0 Intake exhaust terminal vertical concentric Ø 80 125 Intake and Exhaust 26 5 m 1 6 m 4 4 Intake m 11 5 Exhaust m 8 8 Terminal complete with intake exhaust horizontal concentric Ø 80 125 Intake and Exhaust 39 m 2 3 m 6 5 Intake m 16 9 Exhaust m 13 Intake ...

Страница 11: ...al can be extended to a max length of 12 linear metres using insulated pipes Fig 1 28 and limit the length of the Ø 80 normal flue pipe not insulated to just 5 metres Example of installation with direct vertical terminal in partially protected location When the vertical terminal for direct discharge of com bustionfumesisused aminimumgapof300mm mustbeleftbetweentheterminalandthebalcony above The he...

Страница 12: ...re Application with side outlet Fig 1 15 Using the horizontal intake exhaust kit without the special extensions enables routing through a wall thickness of 725 mm with the left side outlet and 645 with the right side outlet Extensions for horizontal kit The Ø 60 100 horizontal intake exhaust kit can be extended up to a max horizontal length of 3000 mm includingtheterminalwithgrilleandexcluding the...

Страница 13: ...bly Fig 1 20 install the concentric flange 2 on the central hole of the boiler inserting the gasket 1 and tighten using the screws in the kit Fit the male end smooth of the adapter 3 into the female end of the concentric flange 2 Imitationaluminiumtileinstallation Replacethe tile with the aluminium sheet 5 shaping it to ensure that rainwater runs off Position the fixed half shell 7 and insert the ...

Страница 14: ...al wall sealing plate has been fitted this will ensure sealing and joining of the elements making up the kit Installation clearances Figure 1 23 gives the min installation space dimensions of the Ø 80 80 separator terminal kit in limited conditions Figure 1 24 shows the configuration with vertical exhaust and horizontal intake Extensions for separator kit Ø 80 80 The max vertical linear length wit...

Страница 15: ...tween the pipe and flue Insulation of separator terminal kit Whenever there are flue gas condensate problems in the exhaust pipes or on the external surface of the intake pipes on request Immergas supplies insulated intake exhaust pipes Insulation my be necessary on the exhaust pipe due to excessive loss of temperature of the flue gas on their route Insulation may be necessary on the intake pipe a...

Страница 16: ... terminals The exhaust terminals must be installed on external perimeter walls of the building be positioned according to the minimum distances specified in current technical standards Combustion products exhaust of natural or fan assisted appliances in open top closed environments In spaces closed on all sides with open tops ventilation pits courtyards etc direct flue gas exhaust is allowed for n...

Страница 17: ...iver turn clockwise and insert the by pass anti clockwise it is excluded 1 21 KITS AVAILABLE ON REQUEST System cut off valves kit The boiler is designed for installation of system interception cocks to be placed on flow and return pipes of the connection assembly This kit is particularly useful for maintenance as it allows the boiler to be drained separately without having to empty the entire syst...

Страница 18: ...l pressure point 10 Negative signal pressure point 11 Flue pressure switch 12 Flow probe 13 Flue hood 14 Safety thermostat 15 Primary heat exchanger 16 Ignition and detection electrodes 17 System expansion vessel 18 Burner 19 System pressure switch 1 22 BOILER COMPONENTS 20 Air vent valve 21 Boiler pump 22 Plate heat exchanger 23 3 way valve motorised 24 System draining valve 25 By pass 26 3 bar s...

Страница 19: ...an checks efficiency of the ducting or other devices Never clean the appliance or connected parts with easily flammable substances Never leave containers or flammable substances in the same environment as the appliance Attention theuseofcomponentsinvolvinguse of electrical power requires some fundamental rules to be observed do not touch the appliance with wet or moist parts of the body do not tou...

Страница 20: ... remote control communication 31 Low power supply voltage 37 Loss of flame signal 38 Block due to loss of continuous flame signal 43 Attention the Anomaly can be reset 5 times consecutively after which the function in inhibited for at least one hour One attempt is gained every hour for a maximum of 5 attempts By switching the appliance on and off the 5 attempts are re acquired Ignition block The b...

Страница 21: ...ILER SHUTDOWN For complete boiler switch off press the off button disconnect the onmipolar switch outside of the boiler and close the gas cock upstream from the appliance Never leave the boiler switched on if left unused for prolonged periods 2 7 RESTORE HEATING SYSTEM PRESSURE Periodically check the system water pressure The boiler manometer should read a pressure between 1 and 1 2 bar If the pre...

Страница 22: ... intake and or exhaust terminals are not blocked check activation of the no air safety pressure switch ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified ensure production of domestic hot water 3 1 HYDRAULIC DIAGRAM ensure sealing efficiency of water circuits check ventilation and or aeration of the installation room where provided If eve...

Страница 23: ...sor software updating operation 3 3 TROUBLESHOOTING N B maintenance interventions must be carried out by a qualified technician e g Immergas After Sales Technical Assistance Service Smell of gas Caused by leakage from gas circuit pipelines Check sealing efficiency of gas intake circuit The fan works but ignition discharge does not occur on the burner ramp The fan may start but the safety air press...

Страница 24: ...ndard setting 0 instant boiler 1 Boiler with storage tank 0 Display lighting Establishes the display lighting mode Display lighting P2 Range of values which can be set Standard setting 0 Off 1 Auto 2 On 1 Off the display is always lit with low intensity Auto the display lights up during use and lowers after 15 seconds of inactivity In the case of anomaly the display flashes On the display is alway...

Страница 25: ...given in the table Par 3 18 3 21 3 7 CHECKS FOLLOWING CONVERSION TO ANOTHER TYPE OF GAS After making sure that conversion was carried out with a nozzle of suitable diameter for the type of gas used and the settings are made at the correct pressure check that there is no flame in the combustion chamber the burner flame is not too high or low and that it is stable does not detach from burner the pre...

Страница 26: ... its activation is signalled by the indication of the flow temperature and the flashing and symbols This function allows the technician to check the combustion parameters Once the function is activated it is possible to select whether to perform the check in CH status regulating the parameters with buttons 5 and 6 or in DHW mode opening any DHW cock and always regulate the parameters with the butt...

Страница 27: ...te boiler maintenance the casing can be completely removed as follows Fig 3 4 3 5 1 Unhook the decorative frame a from the relative lower retainers 2 Remove the decorative frame a from the casing c 3 Loosen the 2 front screws b that fix the casing on 4 Loosen the 2 lower screws d that fix the casing on 5 Pull the case towards yourself c 6 Push the case c upwards at the same time to release it from...

Страница 28: ...28 3 5 4 4 5 6 6 d d c INSTALLER USER MAINTENANCE TECHNICIAN ...

Страница 29: ...ts should therefore be carried out using a differential manometer small U shaped column or digital manometer with the probes inserted in the pressure test gas valve outlet and on the sealed chamber positive pressuretest Thepowerdatainthetablehasbeen obtained with intake exhaust pipe measuring 0 5 m in length Gas flow rates refer to heating power below a temperature of 15 C and at a pressure of 101...

Страница 30: ...urner On Off 5 60 0 06 Central heating circuit max operating pressure bar 3 Central heating circuit max operating temperature C 90 Adjustable central heating temperature C 35 85 System expansion vessel total volume l 4 0 Expansion vessel factory set pressure bar 1 Water content in generator l 2 5 Head available with 1000 l h flow rate kPa m H2 O 24 52 2 5 Hot water production useful heat output kW...

Страница 31: ...SS NOZZLE BURNER GAS FLOW RATE BURNER PRESS NOZZLE BURNER GAS FLOW RATE BURNER PRESS NOZZLE BURNER kW kcal h m3 h mbar mm H2 O kg h mbar mm H2 O kg h mbar mm H2 O 24 0 20640 2 71 12 51 127 6 2 03 29 01 295 8 1 99 36 80 375 3 23 0 19780 2 60 11 53 117 6 1 94 26 65 271 7 1 91 34 07 347 4 22 5 19353 2 55 11 06 112 8 1 90 25 52 260 2 1 87 32 76 334 0 21 0 18060 2 39 9 70 99 0 1 78 22 29 227 3 1 75 28 ...

Страница 32: ...rial Number CHK Check Cod PIN PIN code Type Type of installation Qnw min Minimum heating capacity domestic Qn min Minimum heating capacity heating Qnw max Maximum heating capacity domestic Qn max Maximum heating capacity heating Pn min Minimum heat output Pn max Maximum heat output PMS Maximum pressure system PMW Maximum pressure domestic D Specific flow rate TM Maximum working temperature NOx Cla...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...gas Italia immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038773ENG rev ST 002116 002 12 16 ...

Отзывы: