Parameter Options
The software presents one read-only parameter (Actual Vibration) and several parameters that can be
programmed to optimize performance of the Smart Switch. At any point during the programming process, the
values can be changed between imperial and metric measurements by clicking the Units dropdown in the top
navigation menu and then selecting the appropriate measurement type.
Parameter
Description
Acceptable Value(s)
Actual Vibration
Actual vibration (ips pk) being sensed by the switch at time
when Read Parameters button is clicked.
N/A
MAVT™
Capability to determine and set the alarm threshold value
automatically by the Smart Switch based on the actual
vibration level measured by it. For more information about
the MAVT
™ feature, see page 16.
Enabled
Disabled
Alarm Threshold
Vibration level at which the relay will change state.
0.25- 5.0 ips pk
6.35-127 mm/s pk
Hysteresis
Percentage that actual vibration must fall below the alarm
threshold in order for a non-latching relay to automatically
reset itself. Hysteresis prevents a relay from continually
changing states when the vibration level is hovering around
the alarm threshold level.
3%
6%
10%
Relay Contacts-
Normal State
State in which the relay stays when not tripped.
Normally Open
Normally Closed
Relay Contacts-
Reset State
How the relay operates once actual vibration falls below the
alarm threshold.
Latching: Relay to latch or stay in the alarm state
until manually reset regardless of the vibration level.
Non-Latching Relay automatically resets once the
vibration level falls below the alarm threshold
(hysteresis) level.
Latching
Non-Latching
Power On Delay
Specified time period immediately after power is applied to
the switch during which the relay will not trip regardless of
the vibration level. Prevents a relay trip during high transient
vibration levels that may occur during a normal machine
startup.
3 sec
20 sec
Operation Delay
Specified time period for which actual vibration must
constantly exceed the Alarm Threshold before the relay
changes state. Prevents a relay trip as a result of a short
transient spike in vibration level that may not even be
caused by a machine fault.
1-60 sec
Startup Delay-
Status
Specified time period immediately after power is applied to
the equipment being monitored during which the relay will
not trip regardless of vibration level.
Enabled
Disabled
Startup Delay-
Time Period
Time period during which vibration is ignored.
1-60 sec
1-30 min
Startup Delay-
Startup Alarm Threshold
Maximum vibration ignored during the time period.
Calculated as a multiple of the Alarm Threshold.
2x
4x
8x
Blocked (All vibration)
Startup Delay-
Residual Vibration Level
Minimum vibration level that, once surpassed at equipment
startup, triggers the countdown of the Startup Delay Time
Period.
Dependent
1-40% of Threshold
Independent
0- Alarm Threshold