03/16  10783521 WEB E  cod.MF6HT...

8

Nemo D4-L+

1.6 

Energy pulses 

(where provided)

Quantity that can be coupled: 

active or reactive energy

selects active / reactive

 

confirms

Pulse weight:

1Pulse /0,1kWh(varh) – 1kWh(kvarh) - 10kWh(kvarh) -  100kWh(kvarh)

selects pulse weight

  

confirms

Width of the pulse: 

50 – 100 – 200 – 300ms

selects width of the pulse

confirms

1.7 

Display Contrast

Selectable values

:

1...10

selects the value

confirms

2.0  Password 

2001

Keep simultaneously pressed the

2 keys             

until you display page:

Load 

password 1000

and confirms

 

moves the cursor
increases the loaded value

confirms

2.1 

External CT ratio
Ct =

external primary/secondary CT ratio 

(ex.: CT 800/5A Ct = 160)

External CT ratio (Ct):

1…9999

moves the cursor
increases the loaded value

confirms

Rapporto TV esterni
Vt =

external primary/secondary VT ratio

(ex.: TV 600/100V Vt = 6)

External VT ratio (Vt):

1,0...400,0

moves the cursor
increases the loaded value

confirms

Limit produced ratios 

CT

VT

(CtxVt): 100000 (CT/5A) - 400000(CT/1A)

For voltage direct connection 

(with external voltage transformer)

load 

Vt=1,00

By modifying the 

CT

and/or 

VT

ratios, the KWH meters are automatically 

reset.

Содержание Nemo D4-L+

Страница 1: ...Nemo D4 L Via Travaglia 7 20094 CORSICO MI Tel 02 44 878 1 Fax 02 45 03 448 39 02 45 86 76 63 info imeitaly com www imeitaly com 03 16 10783521 WEB I cod MF6HT...

Страница 2: ...tenza Media pag 4 e 6 1 4 Tempo integrazione corrente e potenza media pag 4 e 6 1 5 Comunicazione RS485 ModBus RTU TCP o BACNET pag 4 5 e 7 1 6 Impulsi energia pag 5 e 8 1 7 Contrasto display pag 5 e...

Страница 3: ...U T VOLTAGE CURRENT 2 5 8 11 2 5 8 11 1 3 4 6 7 9 O U T P U T 33 34 35 RS 485 Rx Tx GND 15 29 20 AUX SUPPLY 21 S 1000 358 3N1E X X X S1 P1 S1 P1 S1 P1 a A L1 L2 L3 N X X X LOAD I N P U T VOLTAGE CURR...

Страница 4: ...o trifase 3 e 4 fili Le inserzioni selezionabili sono 1 3 Potenza media Potenza associata attiva reattiva apparente 1 4 Tempo integrazione corrente e potenza media Tempo integrazione selezionabile 5 8...

Страница 5: ...dotto rapporti TA x TV Ct x Vt 100000 TA 5A 400000 TA 1A Per inserzione diretta in tensione senza TV esterno impostare Vt 1 0 Modificando i rapporti TA e o TV i contatori di energia vengono azzerati a...

Страница 6: ...ffettuati 1 1a Energia Attiva Parziale Azzeramento no no oppure si YES seleziona no o YES conferma 1 1b Picco Corrente media Azzeramento no no oppure si YES seleziona no o YES conferma 1 1c Picco Pote...

Страница 7: ...a pari dispari seleziona parit conferma Tempo di attesa prima della risposta time out 3 100ms sposta il cursore aumenta il valore impostato conferma Normalmente consigliabile impostare 003 3ms In caso...

Страница 8: ...a pagina Impostare password 2001 e confermare sposta il cursore aumenta il valore impostato conferma 2 1 Rapporto TA esterni Ct Rapporto primario secondario TA esterno es TA 800 5A Ct 160 Rapporto TA...

Страница 9: ...03 16 10783521 WEB I cod MF6HT 9 Nemo D4 L 3N3E 3N1E...

Страница 10: ...03 16 10783521 WEB I cod MF6HT 10 Nemo D4 L 3 3E 3 2E 3 1E...

Страница 11: ...03 16 10783521 WEB I cod MF6HT 11 Nemo D4 L 1N1E...

Страница 12: ...8Vca o tensione continua 20 150Vcc In caso di alimentazione in tensione continua rispettare le polarit indicate 20 e 21 F 0 5A gG Alimentazione Ausiliaria I N P U T VOLTAGE CURRENT 2 5 8 11 1 3 4 6 7...

Страница 13: ...Nemo D4 L Via Travaglia 7 20094 CORSICO MI Tel 02 44 878 1 Fax 02 45 03 448 39 02 45 86 76 63 info imeitaly com www imeitaly com 03 16 10783521 WEB E cod MF6HT...

Страница 14: ...8 Display 3 phase 4 wires configuration 3N 3E 3N 1E page 9 3 phase 4 wires configuration 3 3E 3 2E 3 1E page 10 Single phase configuration 1N 1E page 11 Auxiliary Supply page 12 Factory settings page...

Страница 15: ...S1 P1 S 1000 357 3 1E X X X S1 P1 a A L1 L2 L3 N X X X LOAD I N P U T VOLTAGE CURRENT 2 5 8 11 2 5 8 11 1 3 4 6 7 9 O U T P U T 33 34 35 RS 485 Rx Tx GND 15 29 20 AUX SUPPLY 21 S 1000 358 3N1E X X X S...

Страница 16: ...and 4 wire network The selectable connections are 1 3 Power demand Combined power active reactive apparent 1 4 Current delay time and average power Selectable delay time 5 8 10 15 20 30 60 minutes The...

Страница 17: ...al VT ratio Vt 1 0 400 0 Limit produced ratios CT x VT Ct x Vt 100000 CT 5A 400000 CT 1A For voltage direct connection with external voltage transformer load Vt 1 0 By modifying the CT and or VT ratio...

Страница 18: ...1a Partial Active Energy Reset no no or yes YES selects no or YES confirms 1 1b Current Max Demand Reset no no or yes YES selects no or YES confirms 1 1c Power Max Demand Reset no no or yes YES selec...

Страница 19: ...ms Parity bit none even odd selects parity confirms Waiting time before answer time out 3 100ms moves the cursor increases the loaded value confirms It is usually advisable to load 003 3ms If in the c...

Страница 20: ...2 keys until you display page Load password 1000 and confirms moves the cursor increases the loaded value confirms 2 1 External CT ratio Ct external primary secondary CT ratio ex CT 800 5A Ct 160 Exte...

Страница 21: ...03 16 10783521 WEB E cod MF6HT 9 Nemo D4 L 3N3E 3N1E...

Страница 22: ...03 16 10783521 WEB E cod MF6HT 10 Nemo D4 L 3 3E 3 2E 3 1E...

Страница 23: ...03 16 10783521 WEB E cod MF6HT 11 Nemo D4 L 1N1E...

Страница 24: ...ltage 48Vac or direct voltage 20 150Vdc In case of direct voltage supply please respect the shown polarities 20 and 21 F 0 5A gG Auxiliary Supply I N P U T VOLTAGE CURRENT 2 5 8 11 1 3 4 6 7 9 O U T P...

Страница 25: ...Nemo D4 L Via Travaglia 7 20094 CORSICO MI Tel 02 44 878 1 Fax 02 45 03 448 39 02 45 86 76 63 info imeitaly com www imeitaly com 03 16 10783521 WEB F cod MF6HT...

Страница 26: ...ernes page 5 et 8 Affichage Configuration triphas 4 fils 3N 3E 3N 1E page 9 Configuration triphas 3 fils 3 3E 3 2E 3 1E page 10 Configuration monophas 1N 1E page 11 Alimentation auxiliaire page 12 Con...

Страница 27: ...P1 S 1000 357 3 1E X X X S1 P1 a A L1 L2 L3 N X X X LOAD I N P U T VOLTAGE CURRENT 2 5 8 11 2 5 8 11 1 3 4 6 7 9 O U T P U T 33 34 35 RS 485 Rx Tx GND 15 29 20 AUX SUPPLY 21 S 1000 358 3N1E X X X S1 P...

Страница 28: ...eut tre utilis sur r seau monophas ou triphas 3 et 4 fils Les raccordements s lectionnables sont les suivants 1 3 Puissance Moyenne Puissance associ e active r active apparente 1 4 Temps d int gration...

Страница 29: ...00 0 Rapports de produits limit CT x VT Ct x Vt 100000 CT 5A 400000 CT 1A Pour raccordement directe en tension sans TP externe charger Vt 1 0 En modifiant les rapports du CT et ou de TP les compteurs...

Страница 30: ...mptages effectu s 1 1a Energie Active Partielle Remise z ro no no ou oui YES s lectionne no ou YES confirme 1 1b Pic Courant Moyen Remise z ro no no ou oui YES s lectionne no ou YES confirme 1 1c Pic...

Страница 31: ...pair impair s lectionne la parit confirme Temps d attente avant de la r ponse time out 3 100ms d place le curseur augmente la valeur charg e confirme Il est conseillable charger 003 3ms Si dans le br...

Страница 32: ...la suivante page est affich e Charger le mot de passe 2001 et confirmer d place le curseur augmente la valeur charg e confirme 2 1 Rapport CT externes Ct Rapport primaire secondaire CT externe ex CT 8...

Страница 33: ...03 16 10783521 WEB F cod MF6HT 9 Nemo D4 L 3N3E 3N1E...

Страница 34: ...03 16 10783521 WEB F cod MF6HT 10 Nemo D4 L 3 3E 3 2E 3 1E...

Страница 35: ...03 16 10783521 WEB F cod MF6HT 11 Nemo D4 L 1N1E...

Страница 36: ...ion alternative 48Vca ou bien tension continue 20 150Vcc En cas de alimentation en tension continue il faut respecter les polarit s indiqu es 20 et 21 F 0 5A gG I N P U T VOLTAGE CURRENT 2 5 8 11 1 3...

Страница 37: ...Nemo D4 L Via Travaglia 7 20094 CORSICO MI Tel 02 44 878 1 Fax 02 45 03 448 39 02 45 86 76 63 info imeitaly com www imeitaly com 03 16 10783521 WEB D cod MF6HT...

Страница 38: ...setzung Seite 5 und 8 Anzeige 4 Leiter Drehstromnetz 3N 3E 3N 1E Seite 9 3 Leiter Drehstromnetz 3 3E 3 2E 3 1E Seite 10 Wechselstromnetz 1N 1E Seite 11 Hilfsspannung Seite 12 Werkeinstellungen Seite 1...

Страница 39: ...S1 P1 S 1000 357 3 1E X X X S1 P1 a A L1 L2 L3 N X X X LOAD I N P U T VOLTAGE CURRENT 2 5 8 11 2 5 8 11 1 3 4 6 7 9 O U T P U T 33 34 35 RS 485 Rx Tx GND 15 29 20 AUX SUPPLY 21 S 1000 358 3N1E X X X S...

Страница 40: ...m 4 Leiter Drehstromnetz sowie im Wechselstromnetz betrieben werden Folgende Anschlussarten sind m glich 1 3 Mittleren Leistung Verbundene Leistung Wirk Blind oder Scheinleistung 1 4 Stromintegrations...

Страница 41: ...setzung Vt 1 0 400 0 Limit Produktbeziehungen CT x VT Ct x Vt 100000 CT 5A 400000 CT 1A F r direkten Spannungsanschluss ohne externer VT Wandler stellen Vt 1 0 ein Bei Ver nderung von CT und oder Vt w...

Страница 42: ...r ckstellen 1 1a Teilwirkenergie Nullstellung nein no oder ja YES w hlt no oder YES best digt 1 1b Mittlere Stromspitze Nullstellung nein no oder ja YES w hlt no oder YES best digt 1 1c Mittlere Leist...

Страница 43: ...de w hlt die Parit t best digt Zeitsperre vor der Antwort time out 3 100ms verschiebt den Cursor erh ht den eingestellten Wert best digt Es normalweise empfiehlt sich 003 3ms einzustellen Wenn beim An...

Страница 44: ...tigen verschiebt den Cursor erh ht den eingestellten Wert best digt 2 1 Externe Wandler bersetzung Ct Prim r Sekundarverh ltns des externen Stromwandlers z B CT 800 5A Ct 160 Externe CT wandler berse...

Страница 45: ...03 16 10783521 WEB D cod MF6HT 9 Nemo D4 L 3N3E 3N1E...

Страница 46: ...03 16 10783521 WEB D cod MF6HT 10 Nemo D4 L 3 3E 3 2E 3 1E...

Страница 47: ...03 16 10783521 WEB D cod MF6HT 11 Nemo D4 L 1N1E...

Страница 48: ...48V WS oder Gs 20 150V GS gespeist werden kann Im Falle von Gleichspannungsversorgung bitte die angezeigte Polarit ten 20 und 21 beachten F 0 5A gG I N P U T VOLTAGE CURRENT 2 5 8 11 1 3 4 6 7 9 O U T...

Отзывы: