Conto D2
Programmable Parameters
You can access the programming by keeping pressed the key from the total energy display
page.
To program and insert access Password (= 1000) of the KWH meter count start power and
any RS485 address, you have to load a numeric value, whereas for all the other parameters
the choice is made on predetermined fixed steps.
During the setting of the numeric value, the display will show a blinking digit which
automatically will change its position; by pressing the key you will increase the value of
the blinking digit.
In the fixed step settings, by pressing the key you will have the scrolling of the predeter-
mined values.
1 Cd
Access Password
Keep pressed the
Page
key until the page is displayed
Load
Password 1000
Keep pressed the
Page
key until the following page is displayed
2 RS485 communication
(for the models designed for
CE20195A4
)
2.1
Ad
Address number
Selectable values:
1...255
Keep pressed the
Page
key until the following page is displayed
2.2
br
Transmission speed
Selectable values:
2,40 – 4,80 – 9,60 – 19,2 Kbit/s
Keep pressed the
Page
key until the following page is displayed
2.3 Py
Parity Bit
Selectable values:
EVEn
(even) –
odd
(odd) –
nonE
(none)
Keep pressed the
Page
key until the following page is displayed
k Wh