3. Align the PDU with the opening in the side of the rack cabinet; then, while you
hold the PDU in place, attach the brackets to the rack-mounting flanges with
four clip nuts and four M6 screws that come with the PDU.
LA
N
4
3
2
1
6
5
Attention:
You must disconnect the main input power before you connect or
disconnect the input power cord from the PDU.
4. If the PDU comes with a detached power cord, connect the power cord. Align
the connector on the power cord that comes with the PDU with the connector
on the front of the PDU, turning as necessary for key alignment; then, turn the
twist-lock on the connector clockwise until it locks into place.
Key alignment
Twist lock
Chapter 2. Installing the PDU vertically in a rack cabinet
17
Содержание DPI C13 3-phase PDU+
Страница 2: ......
Страница 12: ...x DPI C13 PDU DPI C13 3 phase PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide ...
Страница 22: ...10 DPI C13 PDU DPI C13 3 phase PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide ...
Страница 36: ...24 DPI C13 PDU DPI C13 3 phase PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide ...
Страница 56: ...44 DPI C13 PDU DPI C13 3 phase PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide ...
Страница 62: ...50 DPI C13 PDU DPI C13 3 phase PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide ...
Страница 66: ...54 DPI C13 PDU DPI C13 3 phase PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide ...
Страница 70: ...58 DPI C13 PDU DPI C13 3 phase PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide ...
Страница 78: ...66 DPI C13 PDU DPI C13 3 phase PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide ...
Страница 81: ......
Страница 82: ... Part Number 00D2430 Printed in USA 1P P N 00D2430 ...