PLEASE READ CAREFULLY BEFORE INSTALLATION
INSTALLATION
PROCEDURE
When possible, have a licensed electrician or electrical expert install all
fixtures or aid in the electrical layout plans and/or diagrams prior to
installation.
Check the electrical panel to ensure proper voltage is available for the
number of fixtures installed. Panels should only support a total amperage
of 80% of its capacity. ie 100 amp panel should never exceed 80 amps.
For proper lamp break-in, we recommend that you run the remote ballast
and lamp at 100% power for at least 100 straight hours after initial
startup. This will improve lamp life and performance.
1. Find a suitable location for the ballast with sufficient cooling and
away from any heat source.
2. Install the lamp firmly into the lamp socket of the reflector and connect
the lamp cord to the ballast.
3. Remove the power cord from the box.
4. Plug the power cord into the power source (electrical outlet).
5. Once the lamp has fired, set your desired dimming ratio. Please note
that the ballast dims or raises output gradually to protect the lamp,
so you might not see an instant increase upon changing your output
percentage.
•
Turn the dimming dial to cycle through the dimming levels.
•
If your lamp fails to start immediately, DO NOT cycle the power on
and off. This can damage the lamp and ballast.
•
If after 30 minutes your lamp is still not lit, shut off power to the
ballast, and reconnect.
•
This will begin the startup sequence again.
•
Until the lamp has achieved at least 100 hours of operation, the lamp
should never be turned off prior to running at least 15 minutes. In
case this happens, WAIT 1 hour before igniting the lamp again.
IT IS VERY IMPORTANT
that the lamp is given adequate time to cool
down before it is reignited. Allow a hot lamp to cool for 1 hour before
you try to restrike it. Hot re-strikes cause permanent lamp failure and
lumen output degradations. The lamp should never be turned off before
the lamp reaches full intensity, this may shorten its lifespan.
DO NOT
install ballasts in areas of high heat, such as an attic, tent or
closed closet. Mount units at least 24-60 inches apart.
DIMMING
HOT RESTRIKE
MOUNTING
LOCATION
216mm / 8.50”
278mm / 10.94”
150mm
5.90”
1000W
DE REMOTE BALLAST
ILUMINAR presents the Remote DE ballast. Giving the grower
more GPW than traditional lighting. Available in 750W and
1000W versions gives the grower even more options to
customize their room to whatever specs are required.
Rated Mains Voltage
Voltage Range (+/-10%)
Mains Frequency
Operational Frequency
Dimming Type
Ambient Temperature
Max. Temperature
Relative Humidity
Max. Humidity
Plug Type
Remote Mounting
Ignition Voltage
208-277V
187-290V
50/60Hz
140-220Hz
Gear / 945 / 1000 / EXT
-20...+40°C/-4...+104°F
75°C/167°F
85%
95%
Male NEMA L7-15 Twist Lock
5m/16ft
5kV
OUTPUT SPECIFICATIONS
End of Lamp Life (EOL) Protection
Short Circuit Protection
Open Circuit Protection
Ignition Failure Protection
Thermal Protection
PROTECTIONS
Case Length
Case Width
Height
Weight
PHYSICAL SPECIFICATIONS
278mm
216mm
150mm
4.2kg
10.94"
8.50"
5.90"
9.26lb
Input Volts
Input Current
Input Power
Min Power Factor
THD
Crest Factor
BTU
Inrush Current
240V
4.60A
1045W
0.95
<15%
<1.7
200
≤ 37.5 Amps
INPUT SPECIFICATIONS
208V
5.10A
277V
3.85A
CMH
VOLTAGE:
208V
277V
240V
SKU:
IL-RMCDE1K-277