9850-000857-01. E&OE.
Data LED
Red flashing: Traffic being sent and/or received
Red on: iCAN network comms error
Status LED
Green flashing: Normal operation
DMX LED
Red flashing: DMX data sent
Alarm LED
Red flashing: Alarm data sent
Device Identification Button (IDENT)
Press and release switch.
Sending a message to identify the device on the network
(red Data LED flashes).
Device LEDs and Buttons
Typical Connection Diagram
SCD-96-D
96 Channel DMX Source Controller
Data LED
Status LED
DMX LED
Alarm LED
Network termination
The iCAN network follows a daisy chain topology that
requires termination on the devices located at either
end of the network.
The SCD-96-D unit is supplied with termination
disabled as standard. If it is connected as an end
device in the iCAN network, you need to move the
jumper to enable termination.
To enable SCD-96-D termination, move the jumper
outwards from the inner two pins to the outer two pins:
Termination OFF
Termination ON
iLight Network Termination
Device Identification Button
Alarm Input
DMX Output
Connection to the iLight Network
iCAN
Device
iCAN
Device
SCD-96-D
iCAN network wiring
Cable connections to the iCAN network are made to a removable
5-way connector block located at one end of the SCD-96-D unit:
Function
iCANnet Cable Colours
0V
Black
CAN L
Blue
Shield
Silver
CAN H
White
+VDC
Red
+VDC CAN-H SHIELD CAN-L 0V
Network Power Requirements
Nominal operating voltage: 15V (12-18V)
Nominal operating current: 70mA
Maximum segment distance: 500m (1640 ft)
Devices per segment: 100 (without bridge or repeater)
Additional power supplies may be required.
Consult iLight for information on alternative cable types.
IMPORTANT NOTE:
Connecting a mains potential cable to the
iCAN Network terminals is likley to damage the unit and other
devices connected, and invalidate warranty.