IHP Shiloh36RWS Скачать руководство пользователя страница 6

Comfortflame.US.com

900573-00N/C

6

OPTIONAL OUTSIDE AIR KIT (MODEL AK4/AK4F)

The installation of an outside air kit should be performed during the 

rough framing of the fireplace due to the nature of it's location. Outside 

combustion air is accessed through a vented crawl space (AK4F) or 

through a sidewall (AK4). See Figure 22 on page 13 for instruction of 

operating air kit.

 CAUTION: Combustion air inlet ducts shall not 

terminate in attic space.

The maximum height for the air vent can not exceed 

3 feet below the flue gas outlet of the termination.

HEARTH EXTENSION

A hearth extension projecting a minimum of 20" in front of and a 

minimum of 12" beyond each side of fireplace opening is required 

to protect combustible floor construction in front of fireplace. Fabri

-

cate a hearth extension using a material which meets the following 

specifications: a layer of noncombustible, inorganic material having 

a thermal conductivity of 

k

 = .84 BTU IN/FT

2

 HR °F (or less) at 1" 

thick. For example, if material selected has a k factor of 0.25, such 

as glass fiber, the following formula would apply:
 

0.25 x 1.0" = 0.30" thickness required

  0.84

Thermal conductivity 

"k" 

of materials can be obtained from manu-

facturer or supplier of noncombustible material. If hearth extension 

is to be covered, use noncombustible material such as tile, slate, 

brick, concrete, metal, glass, marble, stone, etc. Provide a means to 

prevent hearth extension from shifting and seal gap between fireplace 

frame and hearth extension with a non-combustible material such as 

sand-cement grout (see Figure 3). 

 WARNING: Hearth extension is to be installed only 

as shown in Figure 3.

Figure 3 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front 

Raised Hearth

Fireplace Front 

Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth 

Extension

MANTELS

A mantel may be installed if desired (see Figure 4). Woodwork such 

as wood trims, mantels or any other combustible material projecting 

from the front face must not be placed within 12" of the fireplace 

opening. Combustible materials above 12" and projecting more than 

1

1

/

2

" from the fireplace must not be placed less than 15" from the 

top opening of the fireplace (NFPA 211, Section - Clearance from 

Combustible Material).

Mantels or any other combustible material also may come up to the 

side edge of the black metal face of the fireplace just as long as the 

projection from the front face fall within the limit shown in Figure 4.

12 

1

/

4

" Ref.

6"

Ref.

12" Min.

9" Min.

1

1

/

2

" Max.

3" Nom.

33°

Combustible 

Material

Safe 

Zone for 

Projection of 

Combustible 

Materials

Fireplace Opening

Upper 

Section of 

Fireplace

Figure 4 - Mantel Clearances to Combustible Material

FIREBOX

SAFE ZONE

Top View of Fireplace

2" Max.

3.0"

Min. to 

Perpendicular 

Side Wall 

12"

8.0"

33°

Combustible 

Material Must 

Not Overlap 

Front Face

FIREPLACE INSTALLATION  

Continued

Содержание Shiloh36RWS

Страница 1: ...re installation to determine the need to obtain a permit POUR LE CANADA L autorité compétente comme le service municipal du bâtiment les pompiers etc doit être contacté avant l installation afin de déterminer la nécessité d obtenir un permis This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes This appli...

Страница 2: ...n and Maintenance Guidelines 13 Replacement Parts 15 Technical Service 15 Parts 16 Accessories 18 Warranty 23 Thank you for your purchase We appreciate your business Please carefully read and follow all instructions in this manual Pay special attention to all warnings and safety information Following these safety care and operation instructions will help ensure many years of dependable and enjoyab...

Страница 3: ...sed to treat insects and fungus When burned thesechemicalscanposeasignificanthazard WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide Poisoning Early signs of carbon monoxidepoisoningresemblethefluwithheadaches dizziness or nausea If you have these signs get fresh air at once Have the appliance inspected by a qualified servic...

Страница 4: ...LE WALL BOARD 0 TO TOP SPACERS NO COMBUSTIBLE MATERIAL ON FACE GAS LINE KNOCK OUTS AIR KIT KNOCK OUT GAS LINE KNOCK OUTS ELECTRICAL OUTLET LEFT SIDE RIGHT SIDE 37 41 35 21 8 22 1 41 1 29 20 1 2 9 1 8 9 1 8 7 1 8 3 1 2 3 1 2 8 3 4 8 3 4 11 1 4 14 1 4 41 1 4 32 1 2 11 3 4 5 8 11 1 2 14 1 2 SQUARE CHASE TOP TERMINATION ROUND TOP TERMINATION CAUTION THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FL...

Страница 5: ...ts air conditioning ducts windows or doors 3 A location that avoids the cutting of joists or roof rafters will make installation easier 4 An outside air kit is available with this fireplace seeOptional Outside Air Kit on page 6 MINIMUM CLEARANCE TO COMBUSTIBLES Ceiling 40 minimum Back and sides of fireplace 3 4 minimum Floor 0 minimum Perpendicular wall to opening 12 minimum Top spacers 0 minimum ...

Страница 6: ...late brick concrete metal glass marble stone etc Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a non combustible material such as sand cement grout see Figure 3 WARNING Hearth extension is to be installed only as shown in Figure 3 Figure 3 Hearth Extension Seal Gap Fireplace Front Ember Protector Fireplace Front Raised Hear...

Страница 7: ... then be installed over the flue pipe section with the hemmed end up Press down on each pipe section until the lances securely engage the hem on the fireplace starter The wire will as sure the proper spacing between the inner and outer pipe sections Continue to assemble chimney sections as outlined making sure that both the inner and outer pipe sections are locked together When installing double w...

Страница 8: ... Detail B Ceiling Support Pipe 12S 8DM USING ELBOW OFFSETS 30E 8DM 1 To achieve desired offset you may install combinations of 12 18 24 36 and 48 length of double wall pipe see offset chart and Figure 7 2 Chimney weight above offset rests on return elbow Straps must be securely nailed to rafters or joists see Figure 8 details A and B 3 Maximum length of pipe between supports return elbow or 12S 8D...

Страница 9: ...rews or Staples Min of 8 Existing Ceiling Frame VENTING INSTALLATION Continued FIRESTOP SPACERS 3600FS 8DM 1 Firestopspacersarerequiredateachpointwherethechimneypenetrates a floor space Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials When the pipe passes through a framed opening into a living space above the firestopmustbeplacedon...

Страница 10: ...s many shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 13 DO NOT NAIL THROUGH FLASHING CONE Installing Flashing on a Metal Roof When installing flashing on a metal roof it is required that putty tape be used between the flashing and roof The flashing must be secured to the roof using 8 x 3 4 screws and then sealed with roof coati...

Страница 11: ...sses through the roof and must be at least 2 feet above the highest point of the roof that is within a horizontal distance of 10 feet see Figure 17 FINISHING FIREPLACE Combustiblematerials suchaswallboard sheetrock drywall plywood etc may make direct contact with sides and top around the fireplace face It is important that combustible materials do not overlap the face itself Brick glass tile or ot...

Страница 12: ...connections must be tested for leaks after the installation is completed After ensuring that the gas valve is on apply soap and water solution to all connections and joints Bubbles formingshowaleak Correctallleaksatonce DONOT USEANOPENFLAMEFORLEAKTESTINGANDDONOT OPERATE ANY APPLIANCE IF A LEAK IS DETECTED LEAK TESTING SHOULD BE DONE BY A QUALIFIED SERVICE PERSON Note An IHP hood must be installed ...

Страница 13: ...e use of the appliance imme diately if doors are damaged and contact a qualified installer for repair Only doors certified with the ap pliance shall be used WARNING Do not slam or strike doors Damage can result in a hazardous condition Cleaning Glass Clean the glass with any commercial glass cleaner or soap and water Do not use any abrasive material to clean the glass Do not clean the glass with a...

Страница 14: ...rth refractory may have shifted or moved out of place while fireplace was in transit These coverplatesmustbekeptintheproperlocationpriortousingthefireplace See Figure 23 For further operating guidelines instructions and warranty infor mation please refer to your homeowner s guide or contact your authorized dealer Figure 23 Locating Access Cover Plate Access Panel ...

Страница 15: ...plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the fireplace 2 The serial number of the fireplace 3 The part number 4 The description of the part 5 The quantity required 6 The installation date of...

Страница 16: ...Comfortflame US com 900573 00N C 16 PARTS 9 24 16 31 25 16 4 30 32 19 12 23 20 28 17 8 1 5 21 2 18 11 14 3 13 22 10 6 29 7 33 34 26 27 15 MODEL NO CATALOG NO Shiloh36RWS F2554 ...

Страница 17: ...ory Brick Liner 1 12 J4472 Bottom Rear Refractory Natural White Brick Liner 1 13 J4474 Bottom Front Refractory Natural White Brick Liner 1 14 J3972 Firebox Support Leg 4 15 Damper Can Collar 1 16 J8012 Kit Screen Assembly 1 17 Firebox Top Assembly 1 18 J3980 Air Kit Door Assembly 1 19 Face Weldment 1 20 J4470 Air Deflector 1 21 Fireplace Top Insulation 1 22 J4052 Access Panel 1 23 J4491 Grate 1 24...

Страница 18: ...Hi Temp Double Wall Pipe Snap Lock F0882 18 8HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock 30 OFFSET AND RETURN F0900 30E 8DM 30 Degree Offset and Return OPTIONAL OUTSIDE AIR KIT FOR FLOOR INSTALLATION F1091 AK4 Complete...

Страница 19: ...F0921 ETL 8DM Square Top with Slip Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SLIP SECTION F0923 ETLO 8DM Square Top with Mesh and Slip Section STAINLESS STEEL HOOD Required when installing a vent free gas log in this fireplace F1052 HS36 36 Stainless Steel Hood w 4 Brow DRAIN PAN...

Страница 20: ... Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT Hi Temp Chimney Support For Use With Chimney Heights In Excess of 30 F0888 RT 8HT Hi Temp Round Top with Mesh Screen F0889 RTT 8HT Hi Temp Round Top with Mesh Screen and Slip Sec tion F0890 RLT 8HT Hi T...

Страница 21: ...________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____________________________________...

Страница 22: ...________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____________________________________...

Страница 23: ...atural or propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided ...

Страница 24: ...ecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2015 IHP LLC P N 900573 00 Rev N C 10 2015 P900573 00 WARRANTY KEEP THIS WARRANTY 1508 Elm Hill Pike Suite 108 Nashville TN 37210 Model Number Serial Number Date Installed Dealer s Name Dealer s Phone Number Keep receipt for warranty verification ...

Отзывы: