IHP GCKSMS557051NP Скачать руководство пользователя страница 2

IHP.US.com

900792-00 NC

2

Millivolt Systems,Natural Gas To Propane Gas Conversion Kits

(SIT Fireplaces)

Cat. No.

Model

Ecoflow Electronic Model Fireplaces

F2898

GCKSMS557051NP DRT4040DMP-B, Altair 40DMP-B

F2902

GCKSMS537051NP DRT4045DMP-B, Altair 45DMP-B

 Table 1

Millivolt Systems, Propane Gas to Natural Gas Conversion Kits

(SIT Fireplaces)

Cat. No.

Model

Ecoflow Electronic Model Fireplace

F2899

GCKSMS425531PN DRT4040DMN-B, Altair 40DMN-B

F2903

GCKSMS415531PN DRT4045DMN-B, Altair 45DMN-B

Table 2

Installing Gas Conversion Kits

 CAUTION 

The gas supply shall be shut OFF prior to discon-

necting the electrical power, before proceeding with 

the conversion.

 ATTENTION 

Avant d’effecteur la conversion, coupez d’abord 

l’alimentation en gaz, ensuite, coupez l’alimentation 

electrique.

Figure 1

Figure 2

       

IMPORTANT

The burner orifice provided in this kit are only for use 

at elevations of 0 to 2,000 feet (610 M) in the USA 

and 0 to 4,500 feet (0-1372 M) in Canada. At higher 

elevations the BTU input must be de-rated by 4% for 

every 1,000 feet (305 M) to maintain the proper ratio 

of gas to air. If the installer must convert the unit to 

adjust for varying altitudes, a deration information 

sticker must be filled out by the installer and adhered 

to the appliance at the time of the conversion. Contact 

your local gas supplier for deration requirements for 

your area.

1.   TURN OFF THE GAS SUPPLY TO THE FIREPLACE and discon-

nect power supply at the circuit breaker. Ensure fireplace is 

cold.

2.   Open the lower control compartment at the bottom front of the 

fireplace door by holding the control compartment door, then 

rotate it away from the fireplace.

3.   Remove the barrier and front glass door/frame from the fire-

place.

4.   Remove the logs. If necessary, remove the log grate. 

NOTE

Exercise care so as not to break the logs.

5.   If applicable, remove ceramic or porcelain firebox liner.

6.   Remove the rear and front burner assemblies. 

NOTE: The rear 

burner air shutter rod is connected to a lever under the firebox.

7.   Rotate the burner to release the air shutter adjustment rod from 

the air shutter lever. Set screws and burner aside for later rein-

stallation.

8.   Refer to the instructions provided with the SIT Regulator Con-

version Kit, and

 Figure 1

. Using a Torx T20 driver (with 1/4” 

shank) or slotted screwdriver, remove and discard the three 

pressure regulator mounting screws, pressure regulator tower, 

the diaphragm assembly (if applicable) and the spring. Discard 

all removed components.

Pressure

Regulator

Remove

These

Components

Pilot

Orifice

Read this instruction sheet in its entirety before beginning the 

installation.
ALL WARNINGS, PRECAUTIONS AND INSTRUCTIONS IN THE 

INSTALLATION AND OPERATION MANUAL PROVIDED WITH THE 

APPLIANCE APPLY TO THESE INSTRUCTIONS.
Check the contents of the kits upon receipt and check for any 

damaged or missing parts. If there is hidden damage, notify 

your freight company or IHP dealer immediately.
INSTALLER NOTICE: THESE INSTRUCTIONS MUST BE LEFT WITH 

THE APPLIANCE.

Содержание GCKSMS557051NP

Страница 1: ... fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency performing this installation is responsible for the proper installation of this kit and assumes responsibility for this conversion The installation is not proper and complete until the operation of the converted appliance is checked as specified in the ma...

Страница 2: ...E and discon nect power supply at the circuit breaker Ensure fireplace is cold 2 Open the lower control compartment at the bottom front of the fireplace door by holding the control compartment door then rotate it away from the fireplace 3 Remove the barrier and front glass door frame from the fire place 4 Remove the logs If necessary remove the log grate NOTE Exercise care so as not to break the l...

Страница 3: ...E Always test pressures with the valve regulator control at the highest setting 18 Affix the appropriate conversion labels see Figures 8 and 9 19 Replace door barrier and optional facade if installed Ensure proper operation with both door and barrier in place NOTE A BARRIER DESIGNED TO REDUCE THE RISK OF BURNS FROM HOT VIEWING GLASS SHALL BE USED DURING OPERA TION OF THIS FIREPLACE FOR THE PROTECT...

Страница 4: ...T4040 B Altair 40 B 28 000 20 000 25 000 18 000 DRT4045 B Altair 45 B 31 000 21 000 31 000 20 000 Table 7 REFERENCE INFORMATION THIS APPLIANCE HAS BEEN CONVERTED ON MM DD YY ________________ TO _____________ GAS WITH KIT NO _______________ BY NAME AND ADDRESS OF ____________ _______________________________________ ORIGANIZATION MAKING THIS CONVERSION WHICH ACCEPTS THE RESPONSIBILITY THAT THIS CONV...

Отзывы: