Index
─
User Manual
17. Hot-Standby Redundancy
Configure column
Tag
using the following identifiers:
#rdcy.IamActive
,
#rdcy.IamPrimary
,
#rdcy.SwitchOverReady
,
#rdcy.MyState
and
#rdcy.PeerState
(refer to Figure 193).
Figure 193 - Definition of internal signals
#rdcy.IamActive
,
#rdcy.IamPrimary
,
#rdcy.SwitchOverReady
,
#rdcy.MyState
and #
rdcy.PeerState
in the iRTU/iGW database using
the iConf configuration tool
The states/values for these internal points are as follows:
o
off
: iRTU/iGW is not active
o
on:
iRTU/iGW is active
o
off
: iRTU/iGW is
Secondary
o
on
: iRTU/iGW is
Primary
o
off
: switchover is not ready
o
on
: switchover is ready
o
0: Unknown state
o
1:
Booting
o
2:
Hearing
o
10:
actAlone
(
Activealone
)
o
11:
actOK
(
ActiveOK
)
o
12:
actSwitchReq
(
Activeswitchoverrequired
)
o
17:
actReboot
(
Activereboot
)
o
30:
Shutdown
o
40:
bckAlone
(
Standbyalone
)
o
41:
bckOK
(
StandbyOK
)
o
42:
bckSwitchReq
(
Standbyswitchoverrequired
)
o
43:
bckSwitchReady
(
Standbyswitchoverready
)
o
44:
bckSwitching
(
Standbyswitching
)
iRTU, iGW & iRTUe Series
156
rdcy.IamActive
rdcy.IamPrimary
rdcy.SwitchOverReady
rdcy.MyState
and
rdcy.PeerState
Содержание iGW Series