MRBP.425241.001-01 UM version 1.1 01.05.2022 FD 330-4-
1 «Vega»
19
3.OPEN THE DETECTORS IN A HAZARDOUS AREA WITH POWER ON
Detector’s housing must be grounded.
Output signal and LED indicators description
FD 330-4-
1 «VEGA» generates the following output signals:
- analogue signal with the following meanings:
a
) (2 ± 0,1) mA – «Failure»;
b
) (4 ± 0,1) mA – «Standard»;
c
) (18 ± 0,1) mA – «Fire»;
d
) (4.1 ± 0,1) mA – «Testing».
- digital signal via standard communication channel RS-485 with MODBUS protocol;
- actuating of the
«dry» contacts of two relays «Fire» and «Failure». Relays are
designed for switching current 1 A at a voltage of 30 VDC.
FD 330-4-
1 «VEGA» is equipped with LED indicators, displaying the current operation
mode of the detector.
Table 1 lists output signals, states of the relay contacts and indicator LEDs for FD
330-4-
1 «VEGA» different states.
Table 1
№
FD 330-4-1
«VEGA» state
«Fire» relay
contacts state
«Failure» relay
contacts state
Output
signal, mA
LED indicators state
1
No supply
voltage
Open
Open
0
Off
2
After switching
on during up to
45 seconds
Open
Open
2
First 5 seconds
continuous, then
flashing yellow glow
3
Dirty optics or
presence of an
object at a
distance of 5-
10 cm from the
entrance
window
Open
Open
2
Periodic switching of
the glow from yellow
to green
4
Failure
Open
Open
2
Continuous yellow
glow
5
Standard
Open
Closed
4
Continuous green
glow
6
Warning
Open
Open
4
Periodic switching of
the glow from green
to red (once a
second)
7
Fire
Closed
Closed
18
Continuous red glow
8
Testing
Open
Closed
4,1
Depending on the
presence of radiation,
one of the above
modes is possible
9
Checking mode
(with a
magnetic key
on)
Open
Open
2
Depending on the
previous mode the
indication remains
It is possible to fix the output signal "Fire" after the end of the alarm cause
.