VSE953

Diagnostic electronics

12

Input (PLC)

Source

Type

Size

Use

Error

Word

2 bytes

“Error code for object state

Hex0000: No fault

Hex0001: Internal fault

Hex0002: Calculation error

Hex0004: Speed out of range

Hex0008: Speed not stable

Hex0010: Invalid baseline

Hex0020: Invalid reference value (1)

Hex0040: Invalid reference value (2)

Hex0100: Deactivated by signal weighting

Hex0200: Reference value out of range

Hex1000: Warning alarm

Hex2000: Damage alarm

Hex8000: Object inactive (by variant)”

Speed

Real

4 bytes

Trigger - rotational speed

Reference
value

Real

4 bytes

Trigger - reference value

Warning
alarm

Real

4 bytes

Limits - warning alarm (relative)

Damage
alarm

Real

4 bytes

Limits - damage alarm (relative)

Baseline

Real

4 bytes

Limits - baseline in SI unit (m/s², m/s)

Frequency range

<object name>

Value

Real

4 bytes

Object value in SI unit 
(m/s², m/s, m)

Status

Byte

1 byte

“(Alarm) state of the object 
0: OK
1: Warning alarm
2: Damage alarm
3: Inactive
4: Error (description: see Error)”

Error

Word

2 bytes

“Error code for object state

Hex0000: No fault

Hex0001: Internal fault

Hex0002: Calculation error

Hex0004: Speed out of range

Hex0008: Speed not stable

Hex0010: Invalid baseline

Hex0020: Invalid reference value (1)

Hex0040: Invalid reference value (2)

Hex0100: Deactivated by signal weighting

Hex0200: Reference value out of range

Hex1000: Warning alarm

Hex2000: Damage alarm

Hex8000: Object inactive (by variant)”

Speed

Real

4 bytes

Trigger - rotational speed

Reference
value

Real

4 bytes

Trigger - reference value

Warning
alarm

Real

4 bytes

Limits - warning alarm (relative)

Damage
alarm

Real

4 bytes

Limits - damage alarm (relative)

Baseline

Real

4 bytes

Limits - baseline in SI unit (m/s², m/s)

Содержание VSE953

Страница 1: ...Operating instructions Diagnostic electronics with Modbus TCP interface for vibration sensors VSE953 11371835 00 03 2021 GB...

Страница 2: ...ction of the sensors 10 7 Modbus TCP 11 7 1 Properties 11 7 2 Data model 11 7 3 Register 14 7 3 1 Device identification register 14 7 3 2 Register mapping input FC4 14 7 4 Input function code 14 7 5 R...

Страница 3: ...ect of the system Read this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditio...

Страница 4: ...ent Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note 2 2 W...

Страница 5: ...Diagnostic electronics VSE953 5 3 Intended use The device has been designed for process value monitoring vibration monitoring and analysis of dynamic signals GB...

Страница 6: ...binary NO NC The outputs can be used for time critical alarms e g machine protection response time up to 1 ms alarm output analogue value output of values measured by the diagnostic electronics The pa...

Страница 7: ...eeded The signals at the inputs are permanently picked up and continuously monitored according to the set parameters With objects in the frequency range unbalance rolling element bearing monitoring is...

Страница 8: ...Observe the guidelines regarding electromagnetic compatibility EMC to keep mechanical risks and interference to a minimum 5 1 Emission This is a class A product The device may cause radio interference...

Страница 9: ...cable length for the inputs IN1 and IN2 30 m w Connect the screen at the sensor w Use a screened sensor cable self assembled The outputs are short circuit proof and can be configured as either normal...

Страница 10: ...safety extra low voltage circuit electrically isolated from other circuits ungrounded when the sensors are connected so that no dangerous contact voltages are applied to the sensor or transferred to...

Страница 11: ...er filing of the output data analogue holding register 16 bits r w Supported function codes FC3 FC4 FC6 FC16 Write max byte length for registers 1 123 registers Read max byte length for registers 1 12...

Страница 12: ...ts baseline in SI unit m s m s Frequency range object name Value Real 4 bytes Object value in SI unit m s m s m Status Byte 1 byte Alarm state of the object 0 OK 1 Warning alarm 2 Damage alarm 3 Inact...

Страница 13: ...otational speed Reference value Real 4 bytes Trigger reference value Warning alarm Real 4 bytes Limits warning alarm relative Damage alarm Real 4 bytes Limits damage alarm relative Counters counter na...

Страница 14: ...e counter Set counter value DINT 4 bytes Set value of the counter selected with the ID in seconds 7 3 Register 7 3 1 Device identification register Address Access Length word Requirement Parameter 390...

Страница 15: ...ata value Code 04 Server device failure 7 8 Factory setting VSE953 Modbus TCP There is read and write access to the device settings The following default values are set by the factory Requirement Para...

Страница 16: ...a the use of the respective function code Examples Reading the register 30001 from the device is done in the master tool by querying the address 0 via FC4 Reading the vendor name in the register 39000...

Страница 17: ...approx 2 Hz No connection has been established an IP address was assigned Green On Device connected to the network Red On Error on the fieldbus LED MOD Modbus TCP IP status n a Off Device is switched...

Страница 18: ...e manufacturer is allowed to repair the unit u After use dispose of the device in an environmentally friendly way in accordance with the applicable national regulations Cleaning the unit u Disconnect...

Отзывы: