Remarks for safe use in hazardous areas

Functions and features

This sensor is used for temperature measurement and is intended for industrial plants. 
The technical data on the type label must be absolutely adhered to. The documentation 
must be observed. For applications in which the failure of the sensor may lead to a risk for 
persons corresponding safety measures must be provided.
•  Use in hazardous areas according to the classification

II 3D

 (group II, category 3D, apparatus for dust atmosphere).

•  The requirements of the standards EN 60079-0 and EN 60079-31 are met. 
•  Marking

II 3D Ex tc IIIC T135°C Dc X    IP67

•  Use in hazardous areas according to the classification

II 3G

 (group II, category 3G, apparatus for gas atmosphere).

•  The requirements of the standards EN 60079-0 and EN 60079-15 are met. 
•  Marking

II  3G  Ex  nA  IIC T4 Gc X

•  Permissible operating temperature of the application (proper usage):

-20°C...+115°C

Installation / Set-up

The units / sensors must only be installed, connected and set up by qualified staff. The 
qualified staff must have knowledge of protection classes, regulations and provisions for 
apparatus in hazardous areas.
Check whether the classification (see "Marking" above and marking on the unit) is suitable 
for the application.
There must be no explosive atmosphere present during any task such as transport, storage, 
mounting, electrical connection, commissioning, maintenance or repair.

Installation remarks / Installation

The temperature sensors must be tightly, firmly and safely connected to the measuring 
application according to the current state of technology. 
•  Adhere to the respective national regulations and provisions as well as the relevant 

installation regulations.

•  It has to be ensured in particular that the sensor has a sufficient heat exchange surface 

with the medium or object to be measured and that faults caused by heat dissipation 
through the thermowell or the cable are kept to a minimum. 

•  The sensor must be firmly and safely connected to its evaluation electronics to ensure a 

permanent electrical connection. 

Содержание TS285A

Страница 1: ...UK Operating instructions Ex protection related part for temperature sensors according to EU directive 2014 34 EU annex VIII ATEX group II equipment category 3D 3G TS285A 80011032 00 02 2019 ...

Страница 2: ...Set up The units sensors must only be installed connected and set up by qualified staff The qualified staff must have knowledge of protection classes regulations and provisions for apparatus in hazardous areas Check whether the classification see Marking above and marking on the unit is suitable for the application There must be no explosive atmosphere present during any task such as transport sto...

Страница 3: ...ectrical characteristic values of the unit must not be exceeded Max operating voltage 6 V Max operating current 10 mA Max power 20 mW Wiring RD RD WH WH Core colours RD red WH white Avoid electrostatic charging on units and cables To avoid electrostatic charging clean the sensor with a damp cloth only Do not mount the sensor in the dust flow Avoid dust deposits on the sensors In any case the user ...

Страница 4: ...sor it must be ensured that no tensile or pressure loads above F 20 Newton are applied on the sensor housing from the cable or vice versa Units or sensors without direct earthing must be installed in an earthed metallic system ensuring a permanent electrical connection and so indirectly earthed Maintenance Repair The unit must not be modified nor can it be repaired In case of a fault please contac...

Страница 5: ...5 UK ...

Отзывы: