SmartPLC DataLine with EtherNet/IP device interface
163
>
Slot 3 – Digital input data single or A slaves, AS-i master 2
41620
Slot
Description
Value range
Length
[words]
3
Digital input data of single or
A slaves, connected to AS-i
master 2
(only available for devices
with 2 AS-i masters)
Empty module = Module is disabled
0
01 ... 03 = Module is active with slaves 1(A) ... 3(A), AS-i Master 2
1
01 ... 07 = Module is active with slaves 1(A) ... 7(A), AS-i Master 2
2
01 ... 11 = Module is active with slaves 1(A) ... 11(A), AS-i Master 2
3
01 ... 15 = Module is active with slaves 1(A) ... 15(A), AS-i Master 2
4
01 ... 19 = Module is active with slaves 1(A) ... 19(A), AS-i Master 2
5
01 ... 23 = Module is active with slaves 1(A) ... 23(A), AS-i Master 2
6
01 ... 27 = Module is active with slaves 1(A) ...27(A), AS-i Master 2
7
01 ... 31 = Module is active with slaves 1(A) ... 31(A), AS-i Master 2
8
Mapping of the digital input/output data:
→
Mapping of the digital input/output data
(
>
Slot 4 – Digital output data single or A slaves, AS-i master 2
41635
Slot
Description
Value range
Length
[words]
4
Digital output data of single
or A slaves, connected to
AS-i master 2
(only available for devices
with 2 AS-i masters)
Empty module = Module is disabled
0
01 ... 03 = Module is active with slaves 1(A) ... 3(A), AS-i Master 2
1
01 ... 07 = Module is active with slaves 1(A) ... 7(A), AS-i Master 2
2
01 ... 11 = Module is active with slaves 1(A) ... 11(A), AS-i Master 2
3
01 ... 15 = Module is active with slaves 1(A) ... 15(A), AS-i Master 2
4
01 ... 19 = Module is active with slaves 1(A) ... 19(A), AS-i Master 2
5
01 ... 23 = Module is active with slaves 1(A) ... 23(A), AS-i Master 2
6
01 ... 27 = Module is active with slaves 1(A) ...27(A), AS-i Master 2
7
01 ... 31 = Module is active with slaves 1(A) ... 31(A), AS-i Master 2
8
Mapping of the digital input/output data:
→
Mapping of the digital input/output data
(