SmartPLC DataLine with EtherNet/IP device interface
110
>
The start screen "Basic settings" appears (→
Start screen 'Basic settings'
(→ S.
>
6.4
Connect and address AS-i slaves
41575
To integrate AS-i slaves into an AS-i network that is controlled by one of the AS-i masters of the
device:
1 Connect and address the AS-i slave
►
Connect ONE AS-i slave to be addressed to the requested AS-i network (AS-i 1 or AS-i 2) as described in the
corresponding installation instructions.
►
Assign the desired address to the AS-i slave
(→
Quick setup: Address the AS-i slaves connected to AS-i Master 1
) or →
Quick setup: Address
the AS-i slaves connected to AS-i Master 2
►
Optional: Repeat step 1 to connect and address further AS-i slaves.
2 Project the AS-i network
►
Carry out a projection adaptation on the AS-i master with the newly addressed AS-i slaves
(→
Quick setup: Project AS-i networks
>
The AS-i master adds the detected slaves (LDS) to the list of the projected slaves (LPS).
>
The AS-i slaves have a valid address and are integrated in the AS-i network.
>
6.5
Setup of EtherNet/IP
41407
Detailed information on how to configure the EtherNet/IP network:
→ operating instructions of
the EtherNet/IP master
To connect the device to the EtherNet/IP network:
►
Select one of the following options:
Use the top-down configuration mode:→
Configuration mode: Top-Down
Use the independent configuration mode: →
Configuration mode: Independent
(→ S.
Before setting the EtherNet/IP parameters, all slaves must be connected to and addressed in
the AS-i network.
► Project the AS-i slaves (→
Connect and address AS-i slaves
(