SmartPLC DataLine with EtherNet/IP device interface
106
>
6.3
Update the firmware of the device
41685
NOTICE!
Interrupting a firmware update leads to a loss of the current system and fieldbus settings.
>
Risk of data loss!
► Secure the device settings before carrying out a firmware update! (→
Export device
configuration
(
► Ensure an uninterrupted voltage supply during the firmware update!
To update the firmware of the device:
►
Select one of the following options:
Firmware update from SD card
Firmware update via the web interface
>
6.3.1
Behaviour of the settings upon firmware update
41532
The following settings/data records remain valid upon a firmware update:
Setting / data record
Path to the menu page
User language of the GUI
[System] > [Setup] > [System settings]
Display settings (screen saver, return)
[System] > [Setup] > [System settings]
System time (date/time)
[System] > [Setup] > [Clock]
NTP settings
[System] > [Setup] > [Clock]
Operating hours counter
[System] > [Diagnosis]
AS-i master settings and configuration data
[AS-i 1] / [AS-i 2] > [Master setup]
IP parameters of the configuration interface
[Interfaces] > [Configuration interface] > [IP-Setup]
Fieldbus settings
[Interfaces] > [EtherNet/IP] > [Setup]
The following settings/data records are reinitalised with their default values upon firmware update:
Setting / data record
Reset value
Path to the menu page
Control of the outputs
Gateway
[System] > [Setup] > [System settings]
Activate CODESYS PLC
deactivated
[System] > [Setup] > [System settings]
Device cycle
0.7 ms
[System] > [Setup] > [System settings]
OSC
Delete system messages
Start page > [OSC]
Retain variables
0x00
--