8.1.1 Explanation of the main menu
Parameters Explanation and setting options
SP1
Switch Point value for volumetric flow on OUT1�
rP1
Reset Switch Point value for volumetric flow on OUT1�
ImPS
Pulse value = volumetric flow quantity at which 1 pulse is provided�
ImPR
Configuration of the output for consumed quantity monitoring:YES (pulse
signal), no (switching signal)�
FEP
Upper flow value at which OUT1 provides the frequency signal FrEP�
FrEP
Frequency signal that is provided at OUT1 when FEP is reached�
OU1
Output function for OUT1 (volumetric flow):
-Hno, Hnc, Fno, Fnc: Switching signal for the limit values
-ImP: Consumed quantity monitoring (totaliser function)
-dOU: Switching signal for empty pipe detection
-FRQ: Frequency output
OU2
Output function for OUT2 (volumetric flow or temperature):
-Hno, Hnc, Fno, Fnc: Switching signal for the limit values
-dOU: Switching signal for empty pipe detection
-I (current signal 4���20 mA), U (voltage signal 0���10 V)
Input function for OUT2:
-In�D: input for external meter reset signal
ASP2
Analogue start point for volumetric flow or temperature on OUT2�
AEP2
Analogue end point for volumetric flow or temperature on OUT2�
SP2
Switch Point value for volumetric flow or temperature on OUT2�
rP2
Reset Switch Point value for volumetric flow or temperature on OUT2�
DIn2
Configuration of the input for external meter reset signal�
EF Extended functions: Opening of the lower menu level�