6

3.2 Sources of interference in the pipe system

Components integrated in the pipes, bends, valves, reductions, etc� lead to  turbu-

lence of the medium� This affects the function of the unit�
Recommendation: Adhere to the distances between sensor and sources of 

interference:

         

         

D = pipe diameter; S = sources of interference

3.3. Mounting operation

 

► Ensure that the system is free of pressure during installation�

 

► Ensure that no media can leak at the mounting location during installa-

tion�

  

 

► Grease the threads of the process connection (1), adapter (2) and nut (3)�

Note: The sensor tip (A) must not be in contact with grease�

 

► Screw the suitable adapter into the process connection�

 

► Place the flow monitor onto the adapter and tighten the nut� Tightening torque 

25 Nm� Ensure that the unit is correctly oriented�

Содержание SI0555

Страница 1: ...Operating instructions Flow monitors SI0555 11458758 00 08 2010 UK...

Страница 2: ...n 6 4 Electrical connection 7 5 Operating and display elements 7 6 Set up and settings for water 8 6 1 Change the switch point optional 8 6 2 High flow adjustment optional 9 7 Additional settings opti...

Страница 3: ...the unit Ensure that the product is suitable for your application without any restrictions The unit conforms to the relevant regulations and EC directives Improper or non intended use may lead to mal...

Страница 4: ...n applies output open if medium is flowing If the flow speed increases the switching status changes when the switch point is reached If the flow speed falls again the switching status changes if the v...

Страница 5: ...ation location General The sensor tip is to be completely sur rounded by the medium Insertion depth of the sensor minimum 12 mm Recommended For horizontal pipes mounting from the side For vertical pip...

Страница 6: ...ces of interference 3 3 Mounting operation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the threads...

Страница 7: ...wer Connect the unit as follows Core colours of ifm sockets 1 BN brown 3 BU blue 4 BK black 5 Operating and display elements 1 Operation display The green LEDs indicate the current flow the LEDs 0 to...

Страница 8: ...2 3 Your normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 6 2 You can restore the factory setting any time 7 3 6 1 Change the switch point optio...

Страница 9: ...you should additionally adapt the unit to the minimum flow Note The following adjustment must only be carried out after the high flow adjust ment Let the minimum flow circulate in the installation or...

Страница 10: ...taneously for at least 10 s in the operating mode The indication goes out the unit locks or unlocks On delivery unlocked 8 Error during adjustment If no adjustment is possible all LEDs flash red The u...

Страница 11: ...the representation range LED 0 flashes current flow far below the represen tation range Interference indicators Short circuit at the switching output The operating indicator and red LEDs light alterna...

Страница 12: ...ton 3 tightening torque 25 Nm 12 Technical data Application area Liquids and gases Operating voltage V 48 DC 10 Current rating mA 250 Short circuit protection pulsed reverse polarity overload protecti...

Страница 13: ...rotection rating IP 67 Protection class III Shock resistance g 50 DIN IEC 68 2 27 11 ms Vibration resistance g 20 DIN IEC 68 2 6 55 2000 Hz Housing materials stainless steel 316L 1 4404 stainless stee...

Отзывы: