SDP110
Air gap sensor
28
10.2.5.4 Output logic
u
Select the CFG menu.
u
Select [P-n] and set PnP or nPn.
10.2.5.5 Measured value damping
u
Select the CFG menu.
u
Select [dAP.F] for flow measurement or [dAP.P] for pressure measurement and set damping
constant in seconds ( τ value 63 %).
10.2.5.6 Measuring nozzle diameter
u
Select the CFG menu.
u
Select [diA] and set the inner diameter of the measuring nozzle(s).
10.2.5.7 Number of measuring nozzles
u
Select the CFG menu.
u
Select [NOZ] and set the number of measuring nozzles.
Only values of 1…5 can be set.
u
For an application with more than 5 measuring nozzles: Select the standard unit "none".
10.2.5.8 Low flow cut-off
u
Select the CFG menu.
u
Select [LFC] and set the limit below which a flow is evaluated as standstill.
10.2.5.9 Standard conditions
u
Select the CFG menu.
u
Select [rEF.P] and set the standard pressure.
u
Select [rEF.T] and set the standard temperature.
10.2.5.10 Zero-point calibration pressure
u
Select the CFG menu.
u
Select [coF] and set value in bar.
w
The internal measured value 0 is shifted by this value.
10.2.5.11 Switch-on /switch-off delay
u
Select the OUTx menu.
u
Select [dSx] and set the delay for switching OUTx in seconds.
u
Select [drx] and set the delay for resetting OUTx in seconds.
10.2.5.12 Error behaviour of the outputs
u
Select the OUTx menu.
u
Select [FOUx] and set the error behaviour for output x: On, OFF, OU.
(More details
Ò
chapters Switching output / Analogue output.)
10.2.5.13 Lock / unlock
The unit can be locked electronically to prevent unintentional settings. Factory setting: not locked.