SB1xxx SB2xxx SB3xxx SB4xxx SB5xxx SB6xxx SB7xxx SB8xxx SB9xxx SB03xx
Mechatronic flow
sensor
26
FL1
/
FL2
FH1
/
FH2
MAW
MEW
Fig. 21: Window function, [coLr] =
Gxou
MAW:
Initial value of the measuring range
MEW:
Final value of the measuring range
FLx:
Lower limit of the window section
FHx:
Upper limit of the window section
10.5.2.1 Parameter setting via unit keys: Display colour setting
u
Call up the menu [EF] > [DIS].
u
Select [coLr] and define the colour of the characters in the process value display.
10.5.2.2 Parameter setting via IO-Link: Display colour setting
u
Call up [Parameters] > [Display Setting].
u
Select [coLr] and define the colour of the characters in the process value display.
10.5.3 Display update rate
The refresh rate of the display can be set via the parameter [diS].
Selectable values:
•
d1: fast (every 50 ms)
•
d2: medium (every 200 ms)
•
d3: slow (every 600 ms)
10.5.3.1 Parameter setting via unit keys: Display update rate
u
Call up the menu [EF] > [DIS].
u
Select [diS] and set the update rate.
10.5.3.2 Parameter setting via IO-Link: Display update rate
u
Call up [Parameters] > [Display Setting].
u
Select [diS. Update rate] and set the update rate.
10.5.4 Display orientation
The text in the display can be rotated for better readability.
10.5.4.1 Parameter setting via unit keys: Display orientation
u
Call up the menu [EF] > [DIS].
u
Select [diS] and set the display rotation simultaneously with the update rate:
•
rd1: every 50 ms and rotated by 180°
•
rd2: every 200 ms and rotated by 180°
•
rd3: every 600 ms and rotated by 180°