20
9.3.2 Setting of the output logic for the switching outputs
►
Select [P-n] and set [PnP] or [nPn]�
9.3.3 Setting of the damping for the switching outputs
►
Select [dAP] and set a value�
dAP value = response time between pressure change and change of the
switching status in milliseconds�
The following fix values can be set; they define the switching frequency (f)
of the output:
dAP
3
6
10
17
30
60
125 250 500
f [Hz] 170
80
50
30
16
8
4
2
1
9.3.4 Configuration of the display
►
Select [diS] and set the update rate and orientation of the display:
-[d1]: update of the measured values every 50 ms�
-[d2]: update of the measured values every 200 ms�
-[d3]: update of the measured values every 600 ms�
-[rd1], [rd2], [rd3]: display as for d1, d2, d3; rotated by 180°�
-[OFF]: the display is switched off in the operating mode�