14
8.2 Explanation of the menu
8.2.1 Explanation of menu level 1
SPx/rPx Upper / lower limit for system pressure at which OUTx switches with hysteresis
setting� Requirement: OUTx setting is [Hno] or [Hnc]�
FHx / FLx Upper / lower limit for system pressure at which OUTx switches with window
setting� Requirement: OUTx setting is [Fno] or [Fnc]�
ASP2
Analogue start point for system pressure: measured value at which 4 mA / 0 V
are provided� Requirement: OUT2 setting is [I] or [U]�
AEP2
Analogue end point for system pressure: measured value at which 20 mA / 10 V
are provided� Requirement: OUT2 setting is [I] or [U]�
EF
Extended functions / opening of menu level 2�
8.2.2 Explanation of menu level 2
rES
Restore factory setting�
ou1
Output function for OUT1:
• Switching signal for the pressure limits: hysteresis function [H ��] or window
function [F ��], either normally open [� no] or normally closed [� nc]�
• Output off [OFF] (function only available in operating mode [3])�
ou2
Output function for OUT2:
• Switching signal for the pressure limits: hysteresis function [H ��] or window
function [F ��], either normally open [� no] or normally closed [� nc]�
• Analogue signal for the current system pressure: 4���20 mA [I] or 0���10 V [U]�
• Output off [OFF] (function only available in operating mode [3])�
dS1 / dS2 Switch-on delay for OUT1 or OUT2�
dr1 / dr2 Switch-off delay for OUT1 / OUT2�
uni
Standard unit of measurement for system pressure (display):
[bAr] / [MPA] / [PSI]�
P-n
Output logic: pnp / npn�
Lo
Minimum value memory for system pressure�
Hi
Maximum value memory for system pressure�
dAP
Damping of the switch point / process data flow (IO-Link communication) and
display�
dAA
Damping of the analogue output�
Requirement: OUT2 setting is [I] or [U]�
coF
Zero-point calibration�
coLr
Assignment of the display colours "red" and "green" within the measuring range�
cFH / cFL Upper / lower value for colour change� Parameter only active after selection of a
freely definable colour window in the coLr parameter: [r-cF] or [G-cF]�
diS
Update rate and orientation of the display�
CMPT
Selection of the operating mode