background image

PI17xx

Electronic pressure sensor

20

CGA

Adjustment of final value of the measuring range between: -5%...+5% of VMR.

diS

Update rate and orientation of the display

SIM

Open the submenu SIM (simulation)

* menu items not active in 2-wire operation

** Time constant tau

8.5 Menu structure: level 3 (simulation)

E

E

E

E

E

E

2

2

S.PRS

S.Tim

S.On

----

3

OFF

2: Change to menu level 2 (extended functions).

8.6 Explanation of menu level 3

S.PRS

Simulation of a pressure / an error state

S.Tim

Simulation duration 1...60 min

S.On

Simulation start/stop

The simulation is interrupted by pressing the [Enter] key.

Содержание PI17 Series

Страница 1: ...Operating instructions Electronic pressure sensor PI17xx 11400145 00 11 2022 GB...

Страница 2: ...5 3 3 Replace filter cover 14 6 Electrical connection 16 7 Operating and display elements 17 8 Menu 18 8 1 Menu structure Main menu 18 8 2 Explanation of the main menu 18 8 3 Menu structure Level 2 ex...

Страница 3: ...8 9 7 1 Set simulation value 28 9 7 2 Set simulation value 28 9 7 3 Switch simulation on off 28 9 7 4 Read overload processes 29 10 Operation 30 10 1 Read set parameters 30 10 2 Change the display in...

Страница 4: ...ls and further information using the QR code on the unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross referenc...

Страница 5: ...his document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restricti...

Страница 6: ...ure Data sheet Avoid static and dynamic overpressure exceeding the indicated pressure rating by taking appropriate measures The indicated bursting pressure must not be exceeded Even if the bursting pr...

Страница 7: ...value Measured temperature value Exceeding and falling below the limits of the measuring range Device status Switching information Parameter setting Device diagnostics events 4 1 IO Link IO Link is a...

Страница 8: ...ransferred to the memory 4 2 4 Optical localisation The sensor can be localised in the plant via the commands Blinken_An Blinken_Aus When the command is used the switching status LEDs flash and IO L i...

Страница 9: ...the menu switching signal for pressure limit Analogue signal proportional to pressure 4 20 mA Analogue signal proportional to pressure 20 4 mA 4 5 Switching function only for 3 wire operation OUTx cha...

Страница 10: ...e 21 5 mA in case of an error MEW MAW AEP ASP P 1 25 0 100 103 13 4 3 8 20 20 5 21 5 mA FOU On 1 2 4 UL OL 3 MEW Fig 3 Output characteristics of the analogue output to Namur 1 Analogue signal 2 Measur...

Страница 11: ...0 Curve of measured values at factory setting V1 V2 Changed curve of measured values Example Change in gradient CGA 105 MEW 100 MEW 95 MEW MEW D A V1 V0 V2 A Output signal D Pressure MEW Final value o...

Страница 12: ...M O ring order no E30123 PEEK sealing ring order no E30124 The PEEK sealing ring is long term stable and maintenance free u When you replace the PEEK sealing ring or change from a PEEK sealing ring to...

Страница 13: ...according to EHEDG Guideline 9 and 35 The device is suited for CIP cleaning in process when installed correctly u Observe the application limits temperature and material resistance according to the d...

Страница 14: ...aphragm 5 3 2 Orientation filter cover Select the installation situation so that the filter cover is horizontal and the condensate can drain off due to gravity 3 1 2 u Ideal orientation 1 The filter c...

Страница 15: ...for the diaphragm on the sensor u Observe the orientation of the filter cover Installation instructions E30139 E30467 When using the closed filter cover there is no more pressure compensation of the...

Страница 16: ...connect power u Connect the unit as follows 4 3 2 1 1 BN 2 WH OUT2 L 1 L 1 BN 2 WH 4 BK 3 BU OUT1 OUT2 L 2 1 2 wire operation 2 3 wire operation Pin Core colour 1 BN Brown 2 WH White 3 BU Blue 4 BK Bl...

Страница 17: ...switched LED 8 Switching status OUT1 on if output 1 is switched 9 Enter button Selection of the parameters and acknowledgement of the parameter values 10 to 11 Arrow keys up and down Setting of the p...

Страница 18: ...FHx FLx Window function upper lower limit value for system pressure at which OUTx switches Requirement OUTx setting is Fno or Fnc ASP2 Analogue start point for system pressure measured value at which...

Страница 19: ...r normally open no or normally closed nc output off Off ou2 Output function for OUT2 Switching signal for the pressure limits hysteresis function H or window function F either normally open no or norm...

Страница 20: ...ulation menu items not active in 2 wire operation Time constant tau 8 5 Menu structure level 3 simulation E E E E E E 2 2 S PRS S Tim S On 3 OFF 2 Change to menu level 2 extended functions 8 6 Explana...

Страница 21: ...t be taken for each parameter setting 1 Select Parameter SP1 rP1 u Press Enter to get to the menu u Press or until the required parameter is displayed 2 Set parameter value 100 120 u Press Enter to ed...

Страница 22: ...ured value is displayed or wait for 30 s w The sensor returns to the process value display If C Loc is displayed when you try to change a parameter value a parameter setting process is active via the...

Страница 23: ...ional settings Locking Loc 10 s u Make sure that the unit is in normal operating mode u Press simultaneously for 10 s w Loc is displayed Loc is briefly displayed if you try to change parameter values...

Страница 24: ...those parameter values that refer to switching functions cannot be selected 9 2 Configure display optional If the unit of measurement uni P has to be changed this needs to be done before setting other...

Страница 25: ...set the function Hno hysteresis function normally open Hnc hysteresis function normally closed Fno window function normally open Fnc window function normally closed I current signal proportional to p...

Страница 26: ...coF Alternatively automatic adjustment of the offset in the range 0 bar 5 u Make sure that no pressure is applied to the system u Press Enter until tCOF appears u Press or and keep it pressed w The c...

Страница 27: ...m value Lo P minimum value Delete memory u Select Hi P or Lo P u Press or and keep pressed until is displayed u Briefly press Enter Hi P Lo P 9 5 2 Reset sensor parameter If rES is to be exited withou...

Страница 28: ...cted u Press Enter S PRS 9 7 2 Set simulation value u Select S Tim u Set time span for simulation u Press Enter Setting range 1 2 3 4 5 10 15 20 30 45 60 min Factory setting 3 min S Tim 9 7 3 Switch s...

Страница 29: ...xceeded for at least 0 5 ms HIPS Setting of the threshold for the overload counter HIPC HIPS The parameters HIPC and HIPS are only available via IO Link communication In case of an interruption of the...

Страница 30: ...Press or until the required parameter is displayed u Briefly press Enter w The unit displays the corresponding parameter value for approx 30 s then it changes to the process value display Alternative...

Страница 31: ...circuit eliminate fault SC2 X OUT2 flashes Short circuit switching output 2 u Check switching output 2 for short circuit eliminate fault SC X OUT1 and OUT2 flash Short circuit switching output 1 and s...

Страница 32: ...r use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations u In case of return shipment ensure that the unit is free from soiling especially fr...

Страница 33: ...bar AEP tAEP 100 VMR dS1 0 0 dr1 0 0 dS2 0 0 dr2 0 0 Uni bAr mbAr FOU1 on FOU2 on P n pnp dAP 0 06 2 00 dAA 0 06 2 00 dis d2 The indicated percentage of the final value of the measuring range VMR of...

Отзывы: