![IFM O5H5 Series Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/ifm/o5h5-series/o5h5-series_operating-instructions_4035094004.webp)
4
6 Settings
6.1 Sensitivity setting
The sensor is to switch when the object is detected
1
►
Position the object.
►
Press [OUT on] for 2 s.
> The sensitivity is set to the object. The LED flashes.
2
►
Remove the object.
►
Press [OUT off] for 2 s.
> The sensitivity is set to the background.
> The LED goes out. The setting operation is completed.
The sensor is not to switch when the object is detected
►
Position the object (see figure 1) and press [OUT off].
►
Remove the object (see figure 2) and press [OUT on].
The settings can also be carried out first without object and then with object.
6.2 Setting of maximum sensitivity
►
Align the sensor so that no light is reflected.
The sensor is to switch when the object is detected
►
First press [OUT on], then [OUT off].
The sensor is to switch when the object is not detected
►
First press [OUT off], then [OUT on].