► Screw the sensor into the adapter and tighten.

 

Max. tightening torque: 20…25 Nm.

 

► After installation check the tank / pipe for ingress resistance.

4  Electrical connection

The unit must be connected by a qualified electrician.

The national and international regulations for the installation of electrical 

equipment must be adhered to. Voltage supply according to EN 50178, 

SELV, PELV.

 

► Disconnect power and connect unit as follows:

Core colours

4

3

2

1

L

L+

4:

3

2:

4

2

1 BN

WH

BK

BU

BK

Black

BN

Brown

BU

Blue

WH

White

5  Operation

When the supply voltage has been applied, the unit is in the operating mode. It 

carries out its evaluation functions and switches the outputs.
Operation indication by LED and output signals:

LED

OUT1

OUT2

Unit ready for operation, no medium detected

Green

OFF

ON

Unit ready for operation, medium detected

Yellow

ON

OFF

no operating voltage

OFF

OFF

OFF

Error / failure

-

OFF

OFF

6  Maintenance, repair, disposal

 

► From time to time check the probe cap for deposits and damage. Clean the unit 

if badly soiled. In case of damage replace the unit.

 

► After removal and before reinstallation of the unit carefully clean the probe neck 

and the installation slot - especially the sealing cone - with appropriate methods 

to ensure that it is resistant to ingress and without dead space.

 

► It is not possible to repair the unit.