UK
9.2 Parameter setting via IO-Link
A PC with USB IO-Link master
(→ 9.2.1)
or a programmed memory plug
(→ 9.2.2)
or a configured IO-Link environment
(→ 9.2.3)
is required to set the parameters�
9.2.1 Parameter setting via PC and IO-Link master
► Prepare PC, software and master. → Observe the operating instructions of the
respective units / software
(→ 5.3.1)
�
► Connect the unit to the USB IO-Link master (→ Accessories).
►
Follow the menu of the IO-Link software�
►
Set the parameters; adjustable parameters
(→ 9.2.4)
�
►
Check if the parameter setting was accepted by the unit� If necessary, read
sensor again�
►
Remove USB IO-Link master and put the unit into operation
(→ 10)
�
9.2.2 Parameter setting via memory plug
Via a memory plug (→ Accessories), a parameter set can be written/transferred to
the unit
(→ 5.3.1)
� This procedure may be used e�g� for duplicating the parameter
setting of one unit to another�
► Load suitable parameter set (e.g. using a PC) to the memory plug
→ observe the operating instructions of the memory plug.
►
Make sure that the sensor has the original factory settings�
►
Connect the memory plug between sensor and socket�
> When voltage is supplied, the parameter set is transferred from the memory
plug to the sensor�
►
Remove the memory plug and put the unit into operation
(→ 10)
�
9.2.3 Parameter setting during operation
► Make sure that the sensor is connected to an IO-Link-capable module (master)
(→ 5.3.1)
�
► Read the sensor using a suitable IO-Link software → observe the operating
instructions of the respective software�
►
Set the parameters; adjustable parameters
(→ 9.2.4)
�
►
Check if the parameter setting was accepted by the unit� If necessary, read
sensor again�
►
Check whether the unit operates reliably�