Capacitive sensor
KI0054
11
The modified basic teach empty state is also recommended if it has not been possible to carry out a
basic teach empty state (e.g. if the sensor is set up on a full tank).
The modified basic teach empty state can be repeated at any time, an adjustment teach full state
already carried out is not affected.
u
Empty the tank until the level is below the sensing face of the device.
w
For NO the LED goes out, for NC the LED lights.
Set the device as normally open (output closes when the tank is full):
u
Press the button [OUT OFF] for at least 6 seconds.
w
While pressing the pushbutton the LED first flashes slowly, after 6 seconds more quickly. After
releasing the pushbutton, the LED goes out.
Set the device as normally closed (output opens when the tank is full):
u
Press the button [OUT ON] for at least 6 seconds.
w
While pressing the pushbutton the LED first flashes slowly, after 6 seconds more quickly. After
releasing the pushbutton, the LED lights continuously.
7.4 Lock / unlock
The device can be locked electronically to prevent unintentional settings. Factory setting: not locked.
Lock / unlock:
u
Press the buttons [OUT ON] and [OUT OFF] at the same time for 10 s.
w
Acknowledgement: LED state changes for a short time (the lit LED goes out briefly or the LED
which is not lit lights briefly).
If the unit does not react, it may be locked.