UK
ioControl
41
Index
S-idx Designation
Data type
Default
Details
0x1018 0x00 Device
identification
Number of
entries
ro
USINT
0x04
Device identification
0x01 Vendor-ID
ro
UDINT
0x0069666D
Vendor ID oft he device according
to CiA specifikation
0x02 Product code ro
STRING
0
Product code of the device
0x03 Revision
number
ro
UDINT
0
Revision number of the device
0x04 Serial
number
ro
UDINT
0
Serial number of the device
0x1003 0x00 Predefined
error field
Number of
entries
rw
UDINT
0
An error list with 4 entries is
supported
0x01 Error history
ro
UDINT
0
Error occured, coded according to
EMCY list
The last error is indicated in the
sub-index 1
0x02 Error history
ro
UDINT
0
Error occured, coded according to
EMCY list
0x03 Error history
ro
UDINT
0
Error occured, coded according to
EMCY list
0x04 Error history
ro
UDINT
0
Error occured, coded according to
EMCY list
0x05 Error history
ro
UDINT
0
Error occured, coded according to
EMCY list
0x1005
COB-ID
synch
message
rw
UDINT
0x0000 0080
Identifier of the synch message
Bit 30 = 0 → device generates no
synch message
Bit 30 = 1 → device generates a
synch message
Bit 29 = 0 → 11 bit ID
Bit 29 = 1 → ID = 0x80 + node ID
0x1006
Communi-
cation cycle
period
rw
UDINT
0
Max� time between 2 synch objects
in [µs]
Control resolution = 1 ms
0x1008
Manufacturer
device name
ro
STRING
CR205x
Device designation (CR2050 or
CR2051 or CR2052)
0x1009
Manufacturer
hardware
version
ro
STRING
V00�00�00
Hardware version