background image

Converter IO-Link sensor ‒ 4…20 mA

EIO104

7

The analogue signal in case of a fault can be set via the parameter [FOU].

4.2 Operating modes

As soon as these are connected, the device detects a large number of IO-Link devices from ifm
automatically.

There are 2 two operating modes in which the device can be used:

Plug&Play with standard process values.

Operation with user-defined process values.

4.2.1 Plug&Play

The device reads the IO-Link data of the connected IO-Link sensors by using the following default
settings:

Reading of the standard values from the process data flow of the sensor.

The process values are further processed in percent.

The measuring range of the sensor is unscaled, i.e. for each respective analogue output, the
measuring range reaches from ASPx (0 % = 4 mA) to AEPx (100 % = 20 mA).

4.2.2 User settings

The following settings can be made by means of a suitable parameter setting software:

Selection of the process value types (pressure, temperature etc.) that are output via OUT1 and
OUT2.

Changeover of the factory set percentage unit of measure to fixed units for the corresponding
process value types.

Scaling of the measuring range via the parameters [ASP] and [AEP].
Restricting the measuring range can be an advantage, e.g. if the sensor is replaced with a sensor
with another measuring range. 
Requirements for a sensor replacement:

– [uni.x] must be set to unit of measure and not to percent.

– The newly installed sensor covers the physical measuring range of the application.

If the user does not scale the measuring range to suit the sensor, the analogue signal will be
exceeded too early or not at all according to the output characteristics 

Ò

 (Fig. 2).

A scaled measuring range does not enhance the resolution of the output signal.
Example: 
A pressure sensor with a measuring range of 0...10 bar is used. The measuring range is scaled
to 2...8 bar. 
When this sensor is replaced with another device with a measuring range of 0...25 bar, the
converter will still output analogue signals of 4…20 mA between 2…8 bar.
When replacing with a unit with a measuring range of 0...5 bar, the converter outputs analogue
signals of 4...14 mA between 2...5 bar.

4.3 IO-Link

This unit has two IO-Link communication interfaces.

M12 connector:

Output for analogue signals

Input for parameter setting using IO-Link software.

Содержание EIO104

Страница 1: ...Operating instructions Converter IO Link sensor 4 20 mA EIO104 80298783 00 08 2021 GB...

Страница 2: ...nalogue output 6 4 2 Operating modes 7 4 2 1 Plug Play 7 4 2 2 User settings 7 4 3 IO Link 7 5 Electrical connection 9 5 1 Mounting the connector 9 5 2 Removing the connector 10 5 3 UL application are...

Страница 3: ...on the unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result i...

Страница 4: ...e architect of the system Read this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental...

Страница 5: ...e converts the process values provided via IO Link signals into analogue signals and outputs them via two analogue current outputs The unit is not suited for environments with particular requirements...

Страница 6: ...between ASP and AEP Operating instructions sensor If the measured value is outside the measuring range or in the event of an internal error the current signal indicated in the following figure is pro...

Страница 7: ...measure to fixed units for the corresponding process value types Scaling of the measuring range via the parameters ASP and AEP Restricting the measuring range can be an advantage e g if the sensor is...

Страница 8: ...ice IO Link is an internationally standardised IO technology IEC 61131 9 for communicating with sensors and actuators General information about IO Link can be found at io link ifm IO Device Descriptio...

Страница 9: ...Output for analogue signals Input for IO Link parameter setting 1 L supply voltage EIO104 sensor L 2 OUT2 analogue Not used 4 OUT1 analogue IO Link parameter setting 3 L supply voltage EIO104 sensor...

Страница 10: ...u Loosen the coupling nut and simultaneously press the connector against the device 5 3 UL application area For use in the USA and Canada u For connecting the device and the IO Link sensor use UL cert...

Страница 11: ...verter IO Link sensor 4 20 mA EIO104 11 6 Operating and display elements 2 1 Fig 4 LEDs 1 LED red Signals an error 2 LED green Is lit during normal operation and when an IO Link communication is detec...

Страница 12: ...etected update the device catalogue for the parameter setting software via the internet u Change the parameter settings in the software u Transfer the parameter settings to the device 7 1 Adjustable p...

Страница 13: ...UT1 OUT2 in case of a fault On The analogue signal goes to 21 5 mA OFF The analogue signal goes to 3 5 mA On OFF Tab 3 Adjustable parameters The sequence of process data values to be read out is defin...

Страница 14: ...range 2 No IO Link communication detected Flashes u Check connections between IO Link device parameter setting software and unit 2 Measured value outside the detec tion zone Flashes Affected output FO...

Страница 15: ...maintenance free u After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations Cleaning the unit u Disconnect the unit from the voltage supp...

Отзывы: